Ilustración técnica — ABB 1SAE231111R0622 — 1SAE231111R0622 — Installation Contactor

Ilustración técnica. Representative component image; exact configuration and appearance may vary. Imágenes solo de referencia. La apariencia de la pieza suministrada puede variar.

ABB

1SAE231111R0622 — Installation Contactor

contactor

Referencia de la pieza: 1SAE231111R0622

ABB ESB25-22N-06 (1SAE231111R0622) is a four-pole DIN-rail installation contactor with two normally open and two normally closed main contacts. It has a 230–240 V AC/DC control coil and a 25 A AC-1/AC-7a rating. The device occupies two modular spacings and has an IP20 protection rating. Verify the control supply, load category and equipment requirements before selection.

¿Busca ABB 1SAE231111R0622? Esta referencia de catálogo está clasificada como «contactor». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.

Disponibilidad bajo consulta

Precio bajo presupuesto

Envío incluidoGarantía y servicioObtener un presupuesto para esta pieza

Especificaciones técnicas

FabricanteABB
Referencia de la pieza1SAE231111R0622
CategoríaElectricidad y control
Product Net Width36 mm
Product Net Depth / Length65 mm
Product Net Height85 mm
Product Net Weight0.235 kg
Number of Main Contacts NO2
Number of Main Contacts NC2
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC0
Number of Poles4P
Rated Operational VoltageMain Circuit 220 V DC
Rated Frequency (f)Control Circuit 400 Hz
Rated Operational Current AC-1 (I e )25 A
Rated Operational Current AC-3 (I e )(230 V) Single Phase, NC 6 A
Rated Operational Current AC-7a (I e )25 A
Rated Operational Current AC-7b (I e )(230 V) Single Phase, NC 6 A
Rated Operational Power AC-1 (P e )(230 V) Single Phase, NC 5.8 kW
Rated Operational Power AC-3 (P e )(230 V) Single Phase, NC 1.3 kW
Rated Operational Power AC-7a (P e )(230 V) Single Phase, NC 5.8 kW
Rated Operational Power AC-7b (P e )(230 V) Single Phase, NC 0.9 kW
Rated Breaking Capacity AC-38 x Ie / AC-3
Rated Making Capacity AC-310 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (I cw )at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A
Rated Insulation Voltage (U i )500 V
Rated Impulse Withstand Voltage (U imp )6 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (U c )230–240 V AC/DC
Power Lossat Rated Operating Conditions AC-1 per Pole 2 W
Published component typeInstallation Contactor
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
MountingDIN rail
Width in modular spacings2
Degree of protectionIP20
Ambient operating temperature−25 to +55 °C

La información del catálogo puede contener errores o estar desactualizada. Las especificaciones completas y los datos verificados están disponibles bajo petición. Confirme con nosotros la referencia y la compatibilidad con su equipo antes de realizar el pedido.

Preguntas sobre el producto

La información investigada sobre esta pieza aún no está disponible en español. Consulte a nuestro equipo.

Obtener un presupuesto para esta pieza

Siéntase como en casa.

Elija su idioma y destino de entrega. El precio final y el envío se confirman en su presupuesto.