Ilustración técnica — ABB 1SAE232111R0140 — 1SAE232111R0140 — Installation Contactor

Ilustración técnica. Representative component image; exact configuration and appearance may vary. Imágenes solo de referencia. La apariencia de la pieza suministrada puede variar.

ABB

1SAE232111R0140 — Installation Contactor

contactor

Referencia de la pieza: 1SAE232111R0140

ABB 1SAE232111R0140 (EN25-40N-01) is a four-pole installation contactor with four normally open main contacts and a 24 V AC/DC control circuit. It is rated 25 A for AC-1 duty and has On, Off and Auto operating positions. The main circuit and load ratings should be checked against the intended application.

¿Busca ABB 1SAE232111R0140? Esta referencia de catálogo está clasificada como «contactor». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.

Disponibilidad bajo consulta

Precio bajo presupuesto

Envío incluidoGarantía y servicioObtener un presupuesto para esta pieza

Especificaciones técnicas

FabricanteABB
Referencia de la pieza1SAE232111R0140
CategoríaElectricidad y control
Product Net Width36 mm
Product Net Depth / Length65 mm
Product Net Height85 mm
Product Net Weight0.25 kg
Number of Main Contacts NO4
Number of Main Contacts NC0
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC0
Number of Poles4P
Rated Operational VoltageMain circuit: 220 V DC; 400 V AC
Rated Frequency (f)Control circuit: 50, 60 or 400 Hz, or DC; main circuit: 50 or 60 Hz, or DC
Rated Operational Current AC-1 (I e )(NO) 25 A
Rated Operational Current AC-3 (I e )9 A, normally open, at 230 V single-phase or 400 V three-phase
Rated Operational Current AC-7a (I e )(NO) 25 A
Rated Operational Current AC-7b (I e )9 A, normally open, at 230 V single-phase or 400 V three-phase
Rated Operational Power AC-1 (P e )5.8 kW at 230 V single-phase; 17.3 kW at 400 V three-phase, normally open
Rated Operational Power AC-3 (P e )1.3 kW at 230 V single-phase; 4 kW at 400 V three-phase, normally open
Rated Operational Power AC-7a (P e )5.8 kW at 230 V single-phase; 17.3 kW at 400 V three-phase, normally open
Rated Operational Power AC-7b (P e )1.3 kW at 230 V single-phase; 4 kW at 400 V three-phase, normally open
Rated Breaking Capacity AC-38 x Ie / AC-3
Rated Making Capacity AC-310 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (I cw )at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A
Rated Insulation Voltage (U i )500 V
Rated Impulse Withstand Voltage (U imp )4 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (U c )24 V AC/DC
Power Lossat Rated Operating Conditions AC-1 per Pole 2 W
Published component typeInstallation Contactor
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Degree of ProtectionIP20
Operating Ambient Temperature-25 to +55 °C
Manual operating positionsOn, Off, Auto
Width in modular spacings2

La información del catálogo puede contener errores o estar desactualizada. Las especificaciones completas y los datos verificados están disponibles bajo petición. Confirme con nosotros la referencia y la compatibilidad con su equipo antes de realizar el pedido.