Ilustración técnica. Representative component image; exact configuration and appearance may vary. Imágenes solo de referencia. La apariencia de la pieza suministrada puede variar.
1SAE232111R0140 — Installation Contactor
contactorReferencia de la pieza: 1SAE232111R0140
ABB 1SAE232111R0140 (EN25-40N-01) is a four-pole installation contactor with four normally open main contacts and a 24 V AC/DC control circuit. It is rated 25 A for AC-1 duty and has On, Off and Auto operating positions. The main circuit and load ratings should be checked against the intended application.
¿Busca ABB 1SAE232111R0140? Esta referencia de catálogo está clasificada como «contactor». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.
Disponibilidad bajo consulta
Especificaciones técnicas
| Fabricante | ABB |
|---|---|
| Referencia de la pieza | 1SAE232111R0140 |
| Categoría | Electricidad y control |
| Product Net Width | 36 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.25 kg |
| Number of Main Contacts NO | 4 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Rated Operational Voltage | Main circuit: 220 V DC; 400 V AC |
| Rated Frequency (f) | Control circuit: 50, 60 or 400 Hz, or DC; main circuit: 50 or 60 Hz, or DC |
| Rated Operational Current AC-1 (I e ) | (NO) 25 A |
| Rated Operational Current AC-3 (I e ) | 9 A, normally open, at 230 V single-phase or 400 V three-phase |
| Rated Operational Current AC-7a (I e ) | (NO) 25 A |
| Rated Operational Current AC-7b (I e ) | 9 A, normally open, at 230 V single-phase or 400 V three-phase |
| Rated Operational Power AC-1 (P e ) | 5.8 kW at 230 V single-phase; 17.3 kW at 400 V three-phase, normally open |
| Rated Operational Power AC-3 (P e ) | 1.3 kW at 230 V single-phase; 4 kW at 400 V three-phase, normally open |
| Rated Operational Power AC-7a (P e ) | 5.8 kW at 230 V single-phase; 17.3 kW at 400 V three-phase, normally open |
| Rated Operational Power AC-7b (P e ) | 1.3 kW at 230 V single-phase; 4 kW at 400 V three-phase, normally open |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A |
| Rated Insulation Voltage (U i ) | 500 V |
| Rated Impulse Withstand Voltage (U imp ) | 4 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 24 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 2 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Degree of Protection | IP20 |
| Operating Ambient Temperature | -25 to +55 °C |
| Manual operating positions | On, Off, Auto |
| Width in modular spacings | 2 |
La información del catálogo puede contener errores o estar desactualizada. Las especificaciones completas y los datos verificados están disponibles bajo petición. Confirme con nosotros la referencia y la compatibilidad con su equipo antes de realizar el pedido.
Preguntas sobre el producto
La información investigada sobre esta pieza aún no está disponible en español. Consulte a nuestro equipo.
Obtener un presupuesto para esta pieza