1SAE342111R0620 — Installation Contactor
contactorReferencia de la pieza: 1SAE342111R0620
ABB 1SAE342111R0620 is an EN40-20N-06 two-pole installation contactor with two normally open main contacts and a 230 V AC/DC control circuit. It is rated 40 A for AC-1 duty and offers On, Off and Auto operation. At 230 V single-phase, its AC-3 rating is 22 A and 3.7 kW. The unit mounts on a DIN rail and is 54 mm wide.
¿Busca ABB 1SAE342111R0620? Esta referencia de catálogo está clasificada como «contactor». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.
Disponibilidad bajo consulta
Especificaciones técnicas
| Fabricante | ABB |
|---|---|
| Referencia de la pieza | 1SAE342111R0620 |
| Categoría | Electricidad y control |
| Product Net Width | 54 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.375 kg |
| Number of Main Contacts NO | 2 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 2P |
| Rated Operational Voltage | Main circuit: 220 V DC; 400 V AC |
| Rated Frequency (f) | Control circuit: 50 Hz, 60 Hz, 400 Hz and DC; main circuit: 50 Hz, 60 Hz and DC |
| Rated Operational Current AC-1 (I e ) | (NO) 40 A |
| Rated Operational Current AC-3 (I e ) | (230 V) Single Phase, NO 22 A |
| Rated Operational Current AC-7a (I e ) | (NO) 40 A |
| Rated Operational Current AC-7b (I e ) | (230 V) Single Phase, NO 22 A |
| Rated Operational Power AC-1 (P e ) | (230 V) Single Phase, NO 9.2 kW |
| Rated Operational Power AC-3 (P e ) | (230 V) Single Phase, NO 3.7 kW |
| Rated Operational Power AC-7a (P e ) | (230 V) Single Phase, NO 9.2 kW |
| Rated Operational Power AC-7b (P e ) | (230 V) Single Phase, NO 3.7 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 176 A |
| Rated Insulation Voltage (U i ) | 500 V |
| Rated Impulse Withstand Voltage (U imp ) | 4 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 230 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 3 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Manual operating modes | On, Off, Auto |
| Mounting | DIN rail |
| Width in modular spacings | 3 |
| Degree of Protection | IP20 |
| Ambient air temperature, operation | -25 to +55 °C |