Ilustración técnica — ABB 1SAL102622R9901 — 1SAL102622R9901 — Mini Contactor

Ilustración técnica. Representative component image; exact configuration and appearance may vary. Imágenes solo de referencia. La apariencia de la pieza suministrada puede variar.

ABB

1SAL102622R9901 — Mini Contactor

contactor

Referencia de la pieza: 1SAL102622R9901

ABB 1SAL102622R9901, model MC1A310AT6, is a three-pole mini contactor with three normally open main contacts and one normally open auxiliary contact. It has a 220–230 V AC control coil for 50/60 Hz, screw terminals and provision for rail or wall mounting. At 400 V, its AC-3 rating is 9 A and 4 kW for a three-phase motor. Confirm the control voltage and load requirements before selection.

¿Busca ABB 1SAL102622R9901? Esta referencia de catálogo está clasificada como «contactor». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.

Disponibilidad bajo consulta

Precio bajo presupuesto

Envío incluidoGarantía y servicioObtener un presupuesto para esta pieza

Especificaciones técnicas

FabricanteABB
Referencia de la pieza1SAL102622R9901
CategoríaElectricidad y control
Product Net Width45 mm
Product Net Depth / Length56 mm
Product Net Height48 mm
Product Net Weight0.17 kg
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC0
Number of Poles3P
Rated Operational VoltageAuxiliary Circuit 690 V AC
Rated Frequency (f)Auxiliary Circuit 50 Hz
Conventional Free-air Thermal Current (I th )Auxiliary Circuit 10 A
Rated Operational Current AC-1 (I e )(690 V) 55 °C 20 A
Rated Operational Current AC-3 (I e )(230 V) 55°C 9 A
Rated Operational Current AC-15 (I e )(240 V) 6 A
Rated Operational Current DC-13 (I e )(24 V) 5 A
Rated Operational Power AC-3 (P e )(230 V) Three Phase 2.2 kW
Rated Breaking Capacity AC-38 x Ie / AC-3
Rated Making Capacity AC-310 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (I cw )at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A
Rated Insulation Voltage (U i )750 V
Rated Impulse Withstand Voltage (U imp )Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Minimum Switching CapacityAuxiliary Circuit 17 V
Coil Operating Limits(acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (U c )220 ... 230 V AC
Power Lossat Rated Operating Conditions AC-1 per Pole 0.7 W
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Published component typeMini Contactor
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Coil frequency50 / 60 Hz
Main circuit terminal typeScrew terminals
Mounting methodRail or wall
Rated Operational Current AC-3 at 400 V9 A at 55 °C
Rated Operational Power AC-3 at 400 V4 kW, three-phase

La información del catálogo puede contener errores o estar desactualizada. Las especificaciones completas y los datos verificados están disponibles bajo petición. Confirme con nosotros la referencia y la compatibilidad con su equipo antes de realizar el pedido.

Preguntas sobre el producto

La información investigada sobre esta pieza aún no está disponible en español. Consulte a nuestro equipo.

Obtener un presupuesto para esta pieza

Siéntase como en casa.

Elija su idioma y destino de entrega. El precio final y el envío se confirman en su presupuesto.