Ilustración técnica — ABB 1SAM250000R1005 — 1SAM250000R1005 — Motor protection circuit-breaker

Ilustración técnica. Representative component image; exact configuration and appearance may vary. Imágenes solo de referencia. La apariencia de la pieza suministrada puede variar.

ABB

1SAM250000R1005 — Motor protection circuit-breaker

Electricidad y control

Referencia de la pieza: 1SAM250000R1005

ABB MS116-1.0 (1SAM250000R1005) is a three-pole motor protection circuit-breaker with screw terminals and an adjustable overload setting of 0.63–1.0 A. It has a rated operational current of 1 A, thermal overload and short-circuit protection, and phase-failure sensitivity. At 400 V AC its rated service short-circuit breaking capacity is 50 kA.

¿Busca ABB 1SAM250000R1005? Esta referencia de catálogo está clasificada como «Electricidad y control». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.

Disponibilidad bajo consulta

Precio bajo presupuesto

Envío incluidoGarantía y servicioObtener un presupuesto para esta pieza

Especificaciones técnicas

FabricanteABB
Referencia de la pieza1SAM250000R1005
CategoríaElectricidad y control
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter MS116-1.0 valid for production date from week 34/2014
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V -Manual Motor Starter MS116
Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length85.6 mm
Product Net Weight0.225 kg
Rated Service Short-Circuit Breaking Capacity (I cs )50 kA at 230 V AC; 50 kA at 400 V AC; 50 kA at 440 V AC; 30 kA at 500 V AC; 30 kA at 690 V AC
Rated Ultimate Short-Circuit Breaking Capacity (I cu )100 kA at 230, 400, 440, 500 and 690 V AC
Rated Instantaneous Short-Circuit Current Setting (I i )12.5 A
Setting Range0.63–1.0 A
Rated Operational Power AC-3 (P e )0.25 kW at 400 V, three-phase
Rated Operational Power AC-3e (P e )(400 V) Three Phase 0.25 kW
Rated Operational VoltageMain circuit: 690 V AC
Rated Operational Current (I e )1 A
Rated Operational Current AC-3 (I e )1 A
Rated Operational Current AC-3e (I e )1 A
Rated Frequency (f)Main circuit: 50/60 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 0.6 ... 1.6 W
Number of Poles3
Conventional Free-air Thermal Current (I th )Main Circuit 1 A
Degree of ProtectionHousing IP20; main circuit terminals IP10
Terminal TypeScrew terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Mounting Position1 ... 6
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Integrated Auxiliary SwitchNo

La información del catálogo puede contener errores o estar desactualizada. Las especificaciones completas y los datos verificados están disponibles bajo petición. Confirme con nosotros la referencia y la compatibilidad con su equipo antes de realizar el pedido.

Preguntas sobre el producto

La información investigada sobre esta pieza aún no está disponible en español. Consulte a nuestro equipo.

Obtener un presupuesto para esta pieza

Siéntase como en casa.

Elija su idioma y destino de entrega. El precio final y el envío se confirman en su presupuesto.