1SAM250000R1009 — Motor protection circuit-breaker

Electricidad y control

Referencia de la pieza: 1SAM250000R1009

ABB 1SAM250000R1009 is the MS116-6.3 three-pole manual motor starter and motor protection circuit-breaker. It has an adjustable 4.0–6.3 A thermal overload setting, trip class 10A and a 2.2 kW AC-3 rating at 400 V. It provides manual motor switching and protection against overload, short circuit and phase failure. Suitability depends on motor and circuit ratings.

¿Busca ABB 1SAM250000R1009? Esta referencia de catálogo está clasificada como «Electricidad y control». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.

Disponibilidad bajo consulta

Precio bajo presupuesto

Envío incluidoGarantía y servicioObtener un presupuesto para esta pieza

Especificaciones técnicas

FabricanteABB
Referencia de la pieza1SAM250000R1009
CategoríaElectricidad y control
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter MS116-6.3
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V -Manual Motor Starter MS116
Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length85.6 mm
Product Net Weight0.265 kg
Rated Service Short-Circuit Breaking Capacity (I cs )50 kA at 230 V AC and 400 V AC; 6 kA at 440 V AC and 500 V AC; 2 kA at 690 V AC
Rated Ultimate Short-Circuit Breaking Capacity (I cu )75 kA at 230 V AC and 400 V AC; 18 kA at 440 V AC; 15 kA at 500 V AC; 3 kA at 690 V AC
Rated Instantaneous Short-Circuit Current Setting (I i )78.8 A
Setting Range4.0–6.3 A
Rated Operational Power AC-3 (P e )2.2 kW at 400 V, three-phase
Rated Operational Power AC-3e (P e )(400 V) Three Phase 2.2 kW
Rated Operational VoltageMain Circuit 690 V AC
Rated Operational Current (I e )6.3 A
Rated Operational Current AC-3 (I e )6.3 A
Rated Operational Current AC-3e (I e )6.3 A
Rated Frequency (f)50/60 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 0.7 ... 1.8 W
Number of Poles3
Conventional Free-air Thermal Current (I th )Main Circuit 6.3 A
Degree of ProtectionHousing IP20
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Mounting Position1 ... 6
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Trip Class10A
Mounting on DIN RailTH35-7.5 or TH35-15, 35 mm DIN rail

La información del catálogo puede contener errores o estar desactualizada. Las especificaciones completas y los datos verificados están disponibles bajo petición. Confirme con nosotros la referencia y la compatibilidad con su equipo antes de realizar el pedido.