Ilustración técnica. Representative component image; exact configuration and appearance may vary. Imágenes solo de referencia. La apariencia de la pieza suministrada puede variar.
1SAM250000R1015 — Motor protection circuit-breaker
Electricidad y controlReferencia de la pieza: 1SAM250000R1015
ABB 1SAM250000R1015 is the MS116-32 manual motor starter and motor protection circuit-breaker. It has a 25–32 A adjustable overload setting, three poles and screw terminals. It provides manual motor switching and protection against overload, short circuits and phase failure. Rated service breaking capacity is 10 kA at 400 V AC.
¿Busca ABB 1SAM250000R1015? Esta referencia de catálogo está clasificada como «Electricidad y control». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.
Disponibilidad bajo consulta
Especificaciones técnicas
| Fabricante | ABB |
|---|---|
| Referencia de la pieza | 1SAM250000R1015 |
| Categoría | Electricidad y control |
| Time-Current Characteristic Curve | Tripping characteristic - Manual Motor Starter MS116-32 |
| Cut-off Current Characteristic | Cut-off Current Characteristic @ 400V -Manual Motor Starter MS116 |
| Product Net Width | 45 mm |
| Product Net Height | 97.8 mm |
| Product Net Depth / Length | 85.4 mm |
| Product Net Weight | 0.31 kg |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | 10 kA at 230 V AC and 400 V AC |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | 16 kA at 230 V AC and 400 V AC |
| Rated Instantaneous Short-Circuit Current Setting (I i ) | 480 A |
| Setting Range | 25–32 A |
| Rated Operational Power AC-3 (P e ) | 15 kW at 400 V AC, three-phase |
| Rated Operational Power AC-3e (P e ) | (400 V) Three Phase 15 kW |
| Rated Operational Voltage | 690 V AC, main circuit |
| Rated Operational Current (I e ) | 32 A |
| Rated Operational Current AC-3 (I e ) | 32 A |
| Rated Operational Current AC-3e (I e ) | 32 A |
| Rated Frequency (f) | 50/60 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Main Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 1.9 ... 3.1 W |
| Number of Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 32 A |
| Degree of Protection | IP20 housing; IP10 main circuit terminals |
| Terminal Type | Screw terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm² |
| Tightening Torque | Main Circuit 2 N·m |
| Wire Stripping Length | Main Circuit 10 mm |
| Mounting Position | 1 ... 6 |
| Published component type | Motor protection circuit-breaker |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip class | 10A |
| DIN rail mounting | TH35-7.5 or TH35-15 |
La información del catálogo puede contener errores o estar desactualizada. Las especificaciones completas y los datos verificados están disponibles bajo petición. Confirme con nosotros la referencia y la compatibilidad con su equipo antes de realizar el pedido.
Preguntas sobre el producto
La información investigada sobre esta pieza aún no está disponible en español. Consulte a nuestro equipo.
Obtener un presupuesto para esta pieza