1SAM360000R1009 — Motor protection circuit-breaker
reléReferencia de la pieza: 1SAM360000R1009
ABB 1SAM360000R1009, type MO132-6.3, is a three-pole magnetic-only manual motor starter rated at 6.3 A. It provides manual switching and short-circuit protection; motor overload protection requires an appropriate thermal or electronic overload relay. The device has screw terminals and a rotary handle.
¿Busca ABB 1SAM360000R1009? Esta referencia de catálogo está clasificada como «relé». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.
Disponibilidad bajo consulta
Especificaciones técnicas
| Fabricante | ABB |
|---|---|
| Referencia de la pieza | 1SAM360000R1009 |
| Categoría | Electricidad y control |
| Time-Current Characteristic Curve | Tripping characteristic - Manual Motor Starter Magnetic Only MO132-4 ... MO132-32 |
| Cut-off Current Characteristic | Cut-off Current Characteristic @ 400V -Manual Motor Starter MS132 |
| Product Net Width | 45 mm |
| Product Net Height | 90 mm |
| Product Net Depth / Length | 86.75 mm |
| Product Net Weight | 0.265 kg |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | (230 V AC) 100 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | (230 V AC) 100 kA |
| Rated Instantaneous Short-Circuit Current Setting (I i ) | 78.8 A |
| Rated Operational Power AC-3 (P e ) | (400 V) Three Phase 2.2 kW |
| Rated Operational Power AC-3e (P e ) | (400 V) Three Phase 2.2 kW |
| Rated Operational Voltage | Main Circuit 690 V AC |
| Rated Operational Current (I e ) | 6.3 A |
| Rated Operational Current AC-3 (I e ) | 6.3 A |
| Rated Operational Current AC-3e (I e ) | 6.3 A |
| Rated Frequency (f) | Main circuit: 50 / 60 Hz |
| Operating Frequency (f sw ) | 0 ... 400 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Main Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 1.1 W |
| Number of Poles | 3P |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 6.3 A |
| Degree of Protection | Housing IP20; main circuit terminals IP10 |
| Terminal Type | Screw Terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Tightening Torque | Main Circuit 0.8 ... 1.2 N·m |
| Wire Stripping Length | Main Circuit 9 mm |
| Mounting Position | 1 ... 6 |
| Published component type | Motor protection circuit-breaker |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Protection type | Magnetic only; separate overload protection required for motors |
| Setting Range | None |
| Mounting on DIN Rail | TH35-15 or TH35-7.5, 35 mm rail |
| Actuator Type | Rotary handle; ON / OFF / TRIP indication |
La información del catálogo puede contener errores o estar desactualizada. Las especificaciones completas y los datos verificados están disponibles bajo petición. Confirme con nosotros la referencia y la compatibilidad con su equipo antes de realizar el pedido.
Preguntas sobre el producto
La información investigada sobre esta pieza aún no está disponible en español. Consulte a nuestro equipo.
Obtener un presupuesto para esta pieza