1SAX341001R1101 — Electronic overload relay
reléReferencia de la pieza: 1SAX341001R1101
ABB 1SAX341001R1101 (EF96-100) is a self-supplied, three-pole electronic motor overload relay with a 36–100 A adjustable setting range. It provides overload and phase-failure protection, selectable trip classes 10E, 20E and 30E, and manual or automatic reset. It has one normally closed trip contact and one normally open signal contact. Confirm the motor, contactor and installation requirements before ordering.
¿Busca ABB 1SAX341001R1101? Esta referencia de catálogo está clasificada como «relé». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.
Disponibilidad bajo consulta
Especificaciones técnicas
| Fabricante | ABB |
|---|---|
| Referencia de la pieza | 1SAX341001R1101 |
| Categoría | Electricidad y control |
| Ex Operating Instructions | ATEX - Operating instructions for EF electronic overload relay for potentially explosive areas |
| Time-Current Characteristic Curve | Tripping characteristic - Electronic overload relay EF19, EF45, EF65, EF96, EF146, EF205, EF370, EF460, EF750 from cold state |
| Product Net Width | 70 mm |
| Product Net Height | 132.7 mm |
| Product Net Depth / Length | 105.2 mm |
| Product Net Weight | 0.802 kg |
| Setting Range | 36–100 A |
| Rated Operational Voltage | Main circuit: 1000 V AC; auxiliary circuit: 600 V AC/DC |
| Rated Operational Current (I e ) | 100 A |
| Rated Frequency (f) | Main circuit: 50/60 Hz; auxiliary circuit: 50/60 Hz or DC |
| Rated Impulse Withstand Voltage (U imp ) | Main circuit: 8 kV; auxiliary circuit: 6 kV |
| Rated Insulation Voltage (U i ) | 1000 V |
| Number of Poles | 3P |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Auxiliary Circuit NC 6 A |
| Rated Operational Current AC-15 (I e ) | (240 V) NC 3 A |
| Rated Operational Current DC-13 (I e ) | (125 V) NC 0.55 A |
| Degree of Protection | Housing: IP20; main circuit terminals: IP10 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Flexible with Ferrule 2x 4 ... 35 mm² |
| Tightening Torque | Auxiliary Circuit 0.8 ... 1.2 N·m |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Mounting Position | 1 ... 6 |
| Power Loss | at Rated Operating Conditions per Pole 0.117 ... 0.9 W |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NC:) B600 |
| Published component type | Electronic overload relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip Class | 10E, 20E or 30E, selectable |
| Reset Mode | Manual or automatic, selectable |
| Ambient Operating Temperature | -25 to +70 °C |