Ilustración técnica. Representative component image; exact configuration and appearance may vary. Imágenes solo de referencia. La apariencia de la pieza suministrada puede variar.
1SAZ721201R1013 — Thermal overload relay
reléReferencia de la pieza: 1SAZ721201R1013
ABB TF42-0.31 (1SAZ721201R1013) is a three-pole electromechanical thermal overload relay for motor protection against overload and phase failure. It has an adjustable 0.23–0.31 A setting range, class 10 tripping, selectable manual or automatic reset, and one normally closed and one normally open auxiliary contact. It connects directly to suitable block contactors; a separate mounting kit is available.
¿Busca ABB 1SAZ721201R1013? Esta referencia de catálogo está clasificada como «relé». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.
Disponibilidad bajo consulta
Especificaciones técnicas
| Fabricante | ABB |
|---|---|
| Referencia de la pieza | 1SAZ721201R1013 |
| Categoría | Electricidad y control |
| Ex Operating Instructions | ATEX - Operating instructions for thermal overload relay TF42 for potentially explosive areas |
| Time-Current Characteristic Curve | Tripping characteristic - Thermal overload relay TF42-0.31 |
| Product Net Width | 45 mm |
| Product Net Height | 88.3 mm |
| Product Net Depth / Length | 70.5 mm |
| Product Net Weight | 0.13 kg |
| Setting Range | 0.23–0.31 A |
| Rated Operational Voltage | Auxiliary circuit: 600 V AC/DC; main circuit: 690 V AC, 600 V DC |
| Rated Operational Current (I e ) | 0.31 A |
| Rated Frequency (f) | Auxiliary Circuit 50 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Auxiliary Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Number of Poles | 3 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Auxiliary Circuit NC 6 A |
| Rated Operational Current AC-15 (I e ) | (120 V) NC 3 A |
| Rated Operational Current DC-13 (I e ) | (125 V) NC 0.55 A |
| Degree of Protection | IP20 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 4 mm² |
| Tightening Torque | Auxiliary Circuit 1 ... 1.2 N·m |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Power Loss | at Rated Operating Conditions per Pole 1.1 ... 2.0 W |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NC:) B600 |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 18-10 AWG |
| Published component type | Thermal overload relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip class | 10 |
| Reset method | Selectable manual or automatic |
| Terminal type | Screw terminals |
La información del catálogo puede contener errores o estar desactualizada. Las especificaciones completas y los datos verificados están disponibles bajo petición. Confirme con nosotros la referencia y la compatibilidad con su equipo antes de realizar el pedido.
Preguntas sobre el producto
La información investigada sobre esta pieza aún no está disponible en español. Consulte a nuestro equipo.
Obtener un presupuesto para esta pieza