LA1SK01 — TeSys SK add-on block with 1 power pole and 1 instantaneous auxiliary contact, for mini contactors LC1SK, LP1SK. It provides 1 power pole (1NO) rated up to 12A/690V AC and 1…
contactorReferencia de la pieza: LA1SK01
LA1SK01 — TeSys SK add-on block with 1 power pole and 1 instantaneous auxiliary contact, for mini contactors LC1SK, LP1SK. It provides 1 power pole (1NO) rated up to 12A/690V AC and 1… — Schneider Electric reference LA1SK01. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.
¿Busca Schneider Electric LA1SK01? Esta referencia de catálogo está clasificada como «contactor». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.
Disponibilidad bajo consulta
Especificaciones técnicas
| Fabricante | Schneider Electric |
|---|---|
| Referencia de la pieza | LA1SK01 |
| Categoría | Gestión de cables y transferencia de energía |
| Range | TeSys |
| product name | TeSys SK |
| Product or Component Type | Power add-on block |
| power pole contact composition | 1P |
| [Ie] rated operational current | 6 A at <= 440 V AC AC-3 for power circuit 12 A (at <131 °F (55 °C)) AC AC-1 for power circuit |
| [Ue] rated operational voltage | Signalling circuit 690 V AC <= 400 Hz Power circuit 690 V AC 50/60 Hz |
| [Ith] conventional free air thermal current | 12 A (at 131 °F (55 °C)) for power circuit 10 A (at 131 °F (55 °C)) for signalling circuit |
| Irms rated making capacity | 66 A at 690 V AC conforming to IEC 60947 66 A at 690 V AC conforming to NF C 63-110 |
| [Icw] rated short-time withstand current | 50 A 131 °F (55 °C) for power circuit |
| Associated fuse rating | 16 A gI at <= 440 V for power circuit conforming to IEC 60947 10 A gI for signalling circuit conforming to IEC 60947 10 A gI for signalling circuit conforming to VDE 0660 |
| [Ui] rated insulation voltage | 690 V IEC 60947 690 V VDE 0110 group C 690 V BS 5424 690 V UL 508 690 V CSA C22.2 No 14 |
| Connections - terminals | connector 1 0.0005…0.009 in² (0.35…6 mm²)flexible with cable end connector 1 0.0008…0.009 in² (0.5…6 mm²)flexible without cable end connector 1 0.002…0.009 in² (1.5…6 mm²)solid connector 2 0.0005…0.002 in² (0.35…1.5 mm²)flexible with cable end connector 2 0.0005…0.004 in² (0.35…2.5 mm²)flexible without cable end connector 2 0.002…0.006 in² (1.5…4 mm²)solid |
| Tightening torque | 7.08 lbf.in (0.8 N.m) connector pozidriv No 1 |
| Signalling circuit frequency | <= 400 Hz |
| Reference status | Published part reference; specification and fitment require confirmation |