Imagen representativa del tipo de componente, no una foto de esta marca o referencia exacta. Confirme la especificación; la pieza suministrada puede tener otro aspecto.
LC1F800 — Contactor
contactorReferencia de la pieza: LC1F800
LC1F800 — Contactor — Schneider Electric reference LC1F800. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.
¿Busca Schneider Electric LC1F800? Esta referencia de catálogo está clasificada como «contactor». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.
Disponibilidad bajo consulta
Especificaciones técnicas
| Fabricante | Schneider Electric |
|---|---|
| Referencia de la pieza | LC1F800 |
| Categoría | Electricidad y control |
| Range | TeSys |
| product name | TeSys F |
| Product or Component Type | Contactor |
| Poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | <= 1000 V AC 50/60 Hz <= 460 V DC |
| [Ie] rated operational current | 1000 A 104 °F (40 °C)) <= 440 V AC AC-1 800 A 131 °F (55 °C)) <= 440 V AC AC-3 |
| Motor power kW | 450 kW at 1000 V AC 50/60 Hz (AC-3) 450 kW at 500 V AC 50/60 Hz (AC-3) 475 kW at 660...690 V AC 50/60 Hz (AC-3) 110 kW at 400 V AC 50/60 Hz (AC-4) 450 kW at 380...400 V AC 50/60 Hz (AC-3) 450 kW at 415 V AC 50/60 Hz (AC-3) 450 kW at 440 V AC 50/60 Hz (AC-3) 250 kW at 220...240 V AC 50/60 Hz (AC-3) |
| [Uc] control circuit voltage | 110...400 V AC 40...400 Hz with LX1/LX9 coil 110...400 V DC with LX4 coil 100...250 V AC 50/60 Hz with LXE coil 100...380 V DC with LXE coil |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 1000 A (at 104 °F (40 °C)) |
| Irms rated making capacity | 8000 A AC conforming to IEC 60947-4-1 |
| Rated breaking capacity | 6400 A conforming to IEC 60947-4-1 |
| [Icw] rated short-time withstand current | 2600 A 104 °F (40 °C) - 3 min 5500 A 104 °F (40 °C) - 10 s 4600 A 104 °F (40 °C) - 30 s 3600 A 104 °F (40 °C) - 1 min 1700 A 104 °F (40 °C) - 10 min |
| Associated fuse rating | 1000 A gG at <= 440 V 800 A aM at <= 440 V |
| Average impedance | 0.12 mOhm - Ith 1000 A 50 Hz |
| [Ui] rated insulation voltage | 1000 V IEC 60947-4-1 1500 V VDE 0110 group C |
| Power dissipation per pole | 120 W AC-1 77 W AC-3 |
| Control circuit voltage limits | Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil Drop-out: 0.3...0.5 Uc AC 40...400 Hz with LX1/LX9 coil Operational: 0.85...1.1 Uc DC with LX4 coil Drop-out: 0.3...0.5 Uc DC with LX4 coil Operational: 85...275 V AC 50/60 Hz with LXE coil Drop-out: 0...60 V AC 50/60 Hz with LXE coil Operational: 85...418 V DC with LXE coil Drop-out: 0...45 V DC with LXE coil |
| Operating time | 60...80 ms closing with LX1/LX9 coil 160...180 ms opening with LX1/LX9 coil 60...80 ms closing with LX4 coil 40...50 ms opening with LX4 coil 40...80 ms closing with LXE coil 6...54 ms opening with LXE coil |
| Mounting Support | Plate |
| Connections - terminals | Power circuit bar 2 60 x 5 mm Power circuit bolted connection Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)solid without cable end Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) |
| Tightening torque | Power circuit 513.3 lbf.in (58 N.m) Control circuit 10.6 lbf.in (1.2 N.m) |
| Inrush power in VA | 1700 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil 1900 VA (at 68 °F (20 °C))with LX4 coil 460…730 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil 500…680 VA cos phi 0.5 (at 68 °F (20 °C))with LXE coil |
| Hold-in power consumption in VA | 12 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil 12 VA (at 68 °F (20 °C))with LX4 coil 7…10 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil 4.0…5.5 VA cos phi 0.5 (at 68 °F (20 °C))with LXE coil |
| Maximum operating rate | 600 cyc/h 131 °F (55 °C) |
| Published component type | Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
La información del catálogo puede contener errores o estar desactualizada. Las especificaciones completas y los datos verificados están disponibles bajo petición. Confirme con nosotros la referencia y la compatibilidad con su equipo antes de realizar el pedido.
Preguntas sobre el producto
La información investigada sobre esta pieza aún no está disponible en español. Consulte a nuestro equipo.
Obtener un presupuesto para esta pieza