Imagen representativa del tipo de componente, no una foto de esta marca o referencia exacta. Confirme la especificación; la pieza suministrada puede tener otro aspecto.
LV430490 — This Micrologic 5.2 A (Ammeter) is a 3 poles 3d electronic trip unit used on Compact NSX 160/250 circuit breakers. This 160A rating electronic trip unit is an optimum choice…
Sensores y automatizaciónReferencia de la pieza: LV430490
LV430490 — This Micrologic 5.2 A (Ammeter) is a 3 poles 3d electronic trip unit used on Compact NSX 160/250 circuit breakers. This 160A rating electronic trip unit is an optimum choice… — Schneider Electric reference LV430490. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.
¿Busca Schneider Electric LV430490? Esta referencia de catálogo está clasificada como «Sensores y automatización». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.
Disponibilidad bajo consulta
Especificaciones técnicas
| Fabricante | Schneider Electric |
|---|---|
| Referencia de la pieza | LV430490 |
| Categoría | Sensores y automatización |
| Range | ComPact |
| Range of Product | ComPact NSX100...250 |
| Product or Component Type | Trip unit |
| Range Compatibility | ComPact NSX160 ComPact NSX250 |
| Number of poles | 3P |
| Protected poles description | 3t |
| Trip unit protection functions | LSI |
| Protection type | L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection |
| Trip unit rated current | 160 A 104 °F (40 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network Frequency | 50/60 Hz |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 63...160 A |
| Long-time protection delay adjustment type tr | Adjustable |
| [tr] long-time protection delay adjustment range | 15…400 s 1.5 x Ir 0.35…11 s 7.2 x Ir 0.5…16 s 6 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable |
| [tsd] Short-time protection delay adjustment range | 0…0.4 s I²t=off 0.1…0.4 s I²t=on |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...15 x In |
| Earth-leakage protection | Without |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
| Display Type | LCD display |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
La información del catálogo puede contener errores o estar desactualizada. Las especificaciones completas y los datos verificados están disponibles bajo petición. Confirme con nosotros la referencia y la compatibilidad con su equipo antes de realizar el pedido.
Preguntas sobre el producto
La información investigada sobre esta pieza aún no está disponible en español. Consulte a nuestro equipo.
Obtener un presupuesto para esta pieza