Imagen de referencia del componente: Published product/series reference; confirm the exact configuration and supplied appearance.

Imagen representativa del tipo de componente, no una foto de esta marca o referencia exacta. Confirme la especificación; la pieza suministrada puede tener otro aspecto.

Schneider Electric

LV433963 — This Micrologic 4.3 AL is a 4 poles 4d electronic trip unit used on Compact NSX 630 circuit breakers. This 570A rating electronic trip unit is an optimum choice for all…

Gestión de cables y transferencia de energía

Referencia de la pieza: LV433963

LV433963 — This Micrologic 4.3 AL is a 4 poles 4d electronic trip unit used on Compact NSX 630 circuit breakers. This 570A rating electronic trip unit is an optimum choice for all… — Schneider Electric reference LV433963. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

¿Busca Schneider Electric LV433963? Esta referencia de catálogo está clasificada como «Gestión de cables y transferencia de energía». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.

Disponibilidad bajo consulta

Precio bajo presupuesto

Envío incluidoGarantía y servicioObtener un presupuesto para esta pieza

Especificaciones técnicas

FabricanteSchneider Electric
Referencia de la piezaLV433963
CategoríaGestión de cables y transferencia de energía
RangeComPact
Range of productComPact NSX400...630
Product or component typeTrip unit
Range compatibilityComPact NSX630
Number of poles4P
Protected poles description4t 3t 3t + N/2
Trip unit protection functionsLSoI
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Trip unit rated current570 A at 40 °C
[Ue] rated operational voltage440 V AC 50/60 Hz
Network frequency50/60 Hz
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range250...570 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
[tsd] Short-time protection delay adjustment range0.02 s
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range6900 A
Earth-leakage protectionIntegrated
Earth-leakage protection classClass A
Earth-leakage protection sensitity adjustment type IΔnAdjustable
[IΔn] earth-leakage protection sensitivity adjustment range3 A 10 A 5 A 1 A 500 mA 300 mA
Earth-leakage protection specific modeOFF using the IΔn rotary switch
Earth-leakage protection time delay adjustement type ΔtAdjustable
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

La información del catálogo puede contener errores o estar desactualizada. Las especificaciones completas y los datos verificados están disponibles bajo petición. Confirme con nosotros la referencia y la compatibilidad con su equipo antes de realizar el pedido.

Preguntas sobre el producto

La información investigada sobre esta pieza aún no está disponible en español. Consulte a nuestro equipo.

Obtener un presupuesto para esta pieza

Siéntase como en casa.

Elija su idioma y destino de entrega. El precio final y el envío se confirman en su presupuesto.