ABB 1SAM340000R1010 is the MS132-10T, a three-pole circuit breaker designed for primary-side control transformer protection. It provides adjustable overload protection from 6.3 to 10 A, a fixed 200 A instantaneous short-circuit setting and manual disconnect operation. The unit has screw terminals and a lockable rotary handle with ON/OFF/TRIP indication.

Vous recherchez ABB 1SAM340000R1010 ? Cette référence de catalogue est classée sous « Électricité et commandes ». Envoyez la référence et les informations sur votre équipement pour vérifier les spécifications et la disponibilité, et obtenir un devis avec livraison incluse.

Disponibilité sur demande

Prix sur devis

Livraison incluseGarantie et serviceObtenir un devis pour cette pièce

Caractéristiques techniques

FabricantABB
Référence de la pièce1SAM340000R1010
CatégorieÉlectricité et commandes
Time-Current Characteristic CurveTripping characteristic - Circuit Breaker for Transformer Protection MS132-10T
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V - Circuit Breaker for Transformer Protection MS132-T / MS132-KT
Product Net Width45 mm
Product Net Height97.8 mm
Product Net Depth / Length86.05 mm
Product Net Weight0.265 kg
Rated Service Short-Circuit Breaking Capacity (I cs )100 kA at 230 V AC and 400 V AC; 30 kA at 440 V AC
Rated Ultimate Short-Circuit Breaking Capacity (I cu )100 kA at 400 V AC
Rated Instantaneous Short-Circuit Current Setting (I i )200 A
Setting Range6.3–10 A
Rated Operational Voltage690 V AC, main circuit
Rated Operational Current (I e )10 A
Rated Frequency (f)50/60 Hz, main circuit
Operating Frequency (f sw )0 ... 400 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 0.7 ... 1.7 W
Number of Poles3
Conventional Free-air Thermal Current (I th )Main Circuit 10 A
Degree of ProtectionHousing IP20; main circuit screw terminals IP10
Terminal TypeScrew terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Mounting Position1 ... 6
Mounting on DIN RailTH35-7.5 or TH35-15, 35 mm rail to IEC 60715
Minimum Mounting DistanceElectrical Conductive Board, Vertical 75 mm
Short-Circuit Current Rating (SCCR)Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA
Published component typePower circuit-breaker for trafo/generator/installation protection
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Overload Trip Class10

Les informations du catalogue peuvent comporter des erreurs ou être obsolètes. Les spécifications complètes et les données vérifiées sont disponibles sur demande. Confirmez avec nous la référence et la compatibilité avec votre équipement avant de commander.

Questions sur le produit

Les résultats de recherche pour cette pièce ne sont pas encore disponibles en français. Contactez notre équipe pour obtenir de l’aide.

Obtenir un devis pour cette pièce

Bienvenue chez vous.

Choisissez votre langue et votre destination de livraison. Le prix final et la livraison seront confirmés dans votre devis.