Illustration technique — ABB 1SAM350000R1001 — 1SAM350000R1001 — Motor protection circuit-breaker

Illustration technique. Representative component image; exact configuration and appearance may vary. Images fournies à titre indicatif. L’apparence de la pièce livrée peut varier.

ABB

1SAM350000R1001 — Motor protection circuit-breaker

Électricité et commandes

Référence de la pièce: 1SAM350000R1001

ABB 1SAM350000R1001 is the MS132-0.16 three-pole manual motor starter, with a 0.10–0.16 A adjustable overload setting. It combines manual motor switching with overload, short-circuit and phase-failure protection. The device has a lockable rotary handle, screw terminals and a 45 mm-wide housing.

Vous recherchez ABB 1SAM350000R1001 ? Cette référence de catalogue est classée sous « Électricité et commandes ». Envoyez la référence et les informations sur votre équipement pour vérifier les spécifications et la disponibilité, et obtenir un devis avec livraison incluse.

Disponibilité sur demande

Prix sur devis

Livraison incluseGarantie et serviceObtenir un devis pour cette pièce

Caractéristiques techniques

FabricantABB
Référence de la pièce1SAM350000R1001
CatégorieÉlectricité et commandes
Ex Operating InstructionsATEX - Operating instructions for Manual Motor Starters MS132 for potentially explosive areas
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter MS132-0.16 valid for production date from week 34/2014
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V -Manual Motor Starter MS132
Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length86.75 mm
Product Net Weight0.215 kg
Rated Service Short-Circuit Breaking Capacity (I cs )100 kA at 400 V AC
Rated Ultimate Short-Circuit Breaking Capacity (I cu )(230 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (I i )2 A
Setting Range0.10–0.16 A
Rated Operational Power AC-3 (P e )(400 V) Three Phase 0.03 kW
Rated Operational Power AC-3e (P e )(400 V) Three Phase 0.03 kW
Rated Operational VoltageMain Circuit 690 V AC
Rated Operational Current (I e )0.16 A
Rated Operational Current AC-3 (I e )0.16 A
Rated Operational Current AC-3e (I e )0.16 A
Rated Operational Current DC-5 (I e )0.16 A
Rated Frequency (f)Main Circuit 50 Hz
Operating Frequency (f sw )0 ... 400 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 0.7 ... 1.7 W
Number of Poles3
Conventional Free-air Thermal Current (I th )Main Circuit 0.16 A
Degree of ProtectionHousing IP20
Terminal TypeScrew terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
MountingStandard DIN rail

Les informations du catalogue peuvent comporter des erreurs ou être obsolètes. Les spécifications complètes et les données vérifiées sont disponibles sur demande. Confirmez avec nous la référence et la compatibilité avec votre équipement avant de commander.

Questions sur le produit

Les résultats de recherche pour cette pièce ne sont pas encore disponibles en français. Contactez notre équipe pour obtenir de l’aide.

Obtenir un devis pour cette pièce

Bienvenue chez vous.

Choisissez votre langue et votre destination de livraison. Le prix final et la livraison seront confirmés dans votre devis.