ABB 1SAM360000R1009, type MO132-6.3, is a three-pole magnetic-only manual motor starter rated at 6.3 A. It provides manual switching and short-circuit protection; motor overload protection requires an appropriate thermal or electronic overload relay. The device has screw terminals and a rotary handle.

Vous recherchez ABB 1SAM360000R1009 ? Cette référence de catalogue est classée sous « relais ». Envoyez la référence et les informations sur votre équipement pour vérifier les spécifications et la disponibilité, et obtenir un devis avec livraison incluse.

Disponibilité sur demande

Prix sur devis

Livraison incluseGarantie et serviceObtenir un devis pour cette pièce

Caractéristiques techniques

FabricantABB
Référence de la pièce1SAM360000R1009
CatégorieÉlectricité et commandes
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter Magnetic Only MO132-4 ... MO132-32
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V -Manual Motor Starter MS132
Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length86.75 mm
Product Net Weight0.265 kg
Rated Service Short-Circuit Breaking Capacity (I cs )(230 V AC) 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (I cu )(230 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (I i )78.8 A
Rated Operational Power AC-3 (P e )(400 V) Three Phase 2.2 kW
Rated Operational Power AC-3e (P e )(400 V) Three Phase 2.2 kW
Rated Operational VoltageMain Circuit 690 V AC
Rated Operational Current (I e )6.3 A
Rated Operational Current AC-3 (I e )6.3 A
Rated Operational Current AC-3e (I e )6.3 A
Rated Frequency (f)Main circuit: 50 / 60 Hz
Operating Frequency (f sw )0 ... 400 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 1.1 W
Number of Poles3P
Conventional Free-air Thermal Current (I th )Main Circuit 6.3 A
Degree of ProtectionHousing IP20; main circuit terminals IP10
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Mounting Position1 ... 6
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Protection typeMagnetic only; separate overload protection required for motors
Setting RangeNone
Mounting on DIN RailTH35-15 or TH35-7.5, 35 mm rail
Actuator TypeRotary handle; ON / OFF / TRIP indication

Les informations du catalogue peuvent comporter des erreurs ou être obsolètes. Les spécifications complètes et les données vérifiées sont disponibles sur demande. Confirmez avec nous la référence et la compatibilité avec votre équipement avant de commander.

Questions sur le produit

Les résultats de recherche pour cette pièce ne sont pas encore disponibles en français. Contactez notre équipe pour obtenir de l’aide.

Obtenir un devis pour cette pièce

Bienvenue chez vous.

Choisissez votre langue et votre destination de livraison. Le prix final et la livraison seront confirmés dans votre devis.