Illustration technique. Representative component image; exact configuration and appearance may vary. Images fournies à titre indicatif. L’apparence de la pièce livrée peut varier.
1SAM461000R1014 — Motor protection circuit-breaker
relaisRéférence de la pièce: 1SAM461000R1014
ABB MO165-32, part 1SAM461000R1014, is a 3-pole magnetic-only manual motor starter rated 32 A. It provides manual switching and short-circuit protection and has screw terminals and a rotary handle. Its AC-3 motor power rating is 15 kW at 400 V, three-phase. A suitable separate thermal or electronic overload relay is required for motor overload protection.
Vous recherchez ABB 1SAM461000R1014 ? Cette référence de catalogue est classée sous « relais ». Envoyez la référence et les informations sur votre équipement pour vérifier les spécifications et la disponibilité, et obtenir un devis avec livraison incluse.
Disponibilité sur demande
Caractéristiques techniques
| Fabricant | ABB |
|---|---|
| Référence de la pièce | 1SAM461000R1014 |
| Catégorie | Électricité et commandes |
| Time-Current Characteristic Curve | Tripping characteristic - Manual Motor Starter Magnetic Only MO165-16 ... MO165-65 |
| Cut-off Current Characteristic | Cut-off Current Characteristic @ 400/690V -Manual Motor Starter MS165/MO165 |
| Product Net Width | 55 mm |
| Product Net Height | 142.65 mm |
| Product Net Depth / Length | 122.1 mm |
| Product Net Weight | 0.97 kg |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | 100 kA at 230 V AC; 100 kA at 400 V AC; 50 kA at 440 V AC; 30 kA at 500 V AC; 10 kA at 690 V AC |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | (230 V AC) 100 kA |
| Rated Instantaneous Short-Circuit Current Setting (I i ) | 480 A |
| Rated Operational Power AC-3 (P e ) | 15 kW at 400 V, three-phase |
| Rated Operational Power AC-3e (P e ) | (400 V) Three Phase 15 kW |
| Rated Operational Voltage | Main circuit: 690 V AC; 250 V DC |
| Rated Operational Current (I e ) | 32 A |
| Rated Operational Current AC-3 (I e ) | 32 A |
| Rated Operational Current AC-3e (I e ) | 32 A |
| Rated Operational Current DC-5 (I e ) | 32 A |
| Rated Frequency (f) | Main circuit: 50 / 60 Hz |
| Operating Frequency (f sw ) | 0 ... 415 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Main Circuit 8 kV |
| Rated Insulation Voltage (U i ) | 1000 V |
| Power Loss | 4.4 W |
| Number of Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 32 A |
| Degree of Protection | Housing IP20; main circuit terminals IP10 |
| Terminal Type | Screw terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 1 ... 35 mm² |
| Tightening Torque | Main Circuit 4 N·m |
| Wire Stripping Length | Main Circuit 16 mm |
| Published component type | Motor protection circuit-breaker |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Protection type | Magnetic-only short-circuit protection; separate overload relay required for motor overload protection. |
| Actuator type | Rotary handle with ON / OFF / TRIP indication |