Illustration technique. Representative component image; exact configuration and appearance may vary. Images fournies à titre indicatif. L’apparence de la pièce livrée peut varier.
1SAX341001R1101 — Electronic overload relay
relaisRéférence de la pièce: 1SAX341001R1101
ABB 1SAX341001R1101 (EF96-100) is a self-supplied, three-pole electronic motor overload relay with a 36–100 A adjustable setting range. It provides overload and phase-failure protection, selectable trip classes 10E, 20E and 30E, and manual or automatic reset. It has one normally closed trip contact and one normally open signal contact. Confirm the motor, contactor and installation requirements before ordering.
Vous recherchez ABB 1SAX341001R1101 ? Cette référence de catalogue est classée sous « relais ». Envoyez la référence et les informations sur votre équipement pour vérifier les spécifications et la disponibilité, et obtenir un devis avec livraison incluse.
Disponibilité sur demande
Caractéristiques techniques
| Fabricant | ABB |
|---|---|
| Référence de la pièce | 1SAX341001R1101 |
| Catégorie | Électricité et commandes |
| Ex Operating Instructions | ATEX - Operating instructions for EF electronic overload relay for potentially explosive areas |
| Time-Current Characteristic Curve | Tripping characteristic - Electronic overload relay EF19, EF45, EF65, EF96, EF146, EF205, EF370, EF460, EF750 from cold state |
| Product Net Width | 70 mm |
| Product Net Height | 132.7 mm |
| Product Net Depth / Length | 105.2 mm |
| Product Net Weight | 0.802 kg |
| Setting Range | 36–100 A |
| Rated Operational Voltage | Main circuit: 1000 V AC; auxiliary circuit: 600 V AC/DC |
| Rated Operational Current (I e ) | 100 A |
| Rated Frequency (f) | Main circuit: 50/60 Hz; auxiliary circuit: 50/60 Hz or DC |
| Rated Impulse Withstand Voltage (U imp ) | Main circuit: 8 kV; auxiliary circuit: 6 kV |
| Rated Insulation Voltage (U i ) | 1000 V |
| Number of Poles | 3P |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Auxiliary Circuit NC 6 A |
| Rated Operational Current AC-15 (I e ) | (240 V) NC 3 A |
| Rated Operational Current DC-13 (I e ) | (125 V) NC 0.55 A |
| Degree of Protection | Housing: IP20; main circuit terminals: IP10 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Flexible with Ferrule 2x 4 ... 35 mm² |
| Tightening Torque | Auxiliary Circuit 0.8 ... 1.2 N·m |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Mounting Position | 1 ... 6 |
| Power Loss | at Rated Operating Conditions per Pole 0.117 ... 0.9 W |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NC:) B600 |
| Published component type | Electronic overload relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip Class | 10E, 20E or 30E, selectable |
| Reset Mode | Manual or automatic, selectable |
| Ambient Operating Temperature | -25 to +70 °C |
Les informations du catalogue peuvent comporter des erreurs ou être obsolètes. Les spécifications complètes et les données vérifiées sont disponibles sur demande. Confirmez avec nous la référence et la compatibilité avec votre équipement avant de commander.
Questions sur le produit
Les résultats de recherche pour cette pièce ne sont pas encore disponibles en français. Contactez notre équipe pour obtenir de l’aide.
Obtenir un devis pour cette pièce