1SAX351001R1101 — Electronic overload relay
relaisRéférence de la pièce: 1SAX351001R1101
ABB 1SAX351001R1101 is the EF146-150 self-supplied electronic overload relay for motor overload and phase-failure protection. It has a 54–150 A adjustable setting range, selectable 10E, 20E and 30E trip classes, and manual or automatic reset. The three-pole relay includes one normally closed trip contact and one normally open signal contact, plus STOP and TEST functions.
Vous recherchez ABB 1SAX351001R1101 ? Cette référence de catalogue est classée sous « relais ». Envoyez la référence et les informations sur votre équipement pour vérifier les spécifications et la disponibilité, et obtenir un devis avec livraison incluse.
Disponibilité sur demande
Caractéristiques techniques
| Fabricant | ABB |
|---|---|
| Référence de la pièce | 1SAX351001R1101 |
| Catégorie | Électricité et commandes |
| Ex Operating Instructions | ATEX - Operating instructions for EF electronic overload relay for potentially explosive areas |
| Time-Current Characteristic Curve | Tripping characteristic - Electronic overload relay EF19, EF45, EF65, EF96, EF146, EF205, EF370, EF460, EF750 from cold state |
| Product Net Width | 89.05 mm |
| Product Net Height | 150.4 mm |
| Product Net Depth / Length | 105.2 mm |
| Product Net Weight | 0.879 kg |
| Setting Range | 54–150 A |
| Rated Operational Voltage | Main circuit: 1000 V AC; auxiliary circuit: 600 V AC/DC |
| Rated Operational Current (I e ) | 150 A |
| Rated Frequency (f) | Main circuit: 50/60 Hz; auxiliary circuit: DC, 50/60 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Auxiliary Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 1000 V |
| Number of Poles | 3 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Auxiliary Circuit NC 6 A |
| Rated Operational Current AC-15 (I e ) | (240 V) NC 3 A |
| Rated Operational Current DC-13 (I e ) | (125 V) NC 0.55 A |
| Degree of Protection | Housing: IP20; main circuit terminals: IP10 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1x 10 ... 70 mm² |
| Tightening Torque | Auxiliary Circuit 0.8 ... 1.2 N·m |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Mounting Position | 1 ... 6 |
| Power Loss | at Rated Operating Conditions per Pole 0.204 ... 1.575 W |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NC:) B600 |
| Published component type | Electronic overload relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip Class | 10E, 20E or 30E, selectable |
| Reset | Manual or automatic, selectable |
| Ambient Operating Temperature | −25 to +70 °C, temperature compensated |