Illustration technique. Representative component image; exact configuration and appearance may vary. Images fournies à titre indicatif. L’apparence de la pièce livrée peut varier.
1SAZ711201R1047 — Thermal overload relay
relaisRéférence de la pièce: 1SAZ711201R1047
ABB 1SAZ711201R1047 is the T16-16 three-pole thermal overload relay, with an adjustable 13–16 A setting and class 10 trip characteristic. It provides motor overload and phase-failure protection, with selectable manual or automatic reset, one normally closed trip contact and one normally open signal contact. Separate short-circuit protection is required.
Vous recherchez ABB 1SAZ711201R1047 ? Cette référence de catalogue est classée sous « relais ». Envoyez la référence et les informations sur votre équipement pour vérifier les spécifications et la disponibilité, et obtenir un devis avec livraison incluse.
Disponibilité sur demande
Caractéristiques techniques
| Fabricant | ABB |
|---|---|
| Référence de la pièce | 1SAZ711201R1047 |
| Catégorie | Électricité et commandes |
| Time-Current Characteristic Curve | Tripping characteristic - Thermal overload relay T16-16 |
| Product Net Width | 45 mm |
| Product Net Height | 76.7 mm |
| Product Net Depth / Length | 53.5 mm |
| Product Net Weight | 0.104 kg |
| Setting Range | 13–16 A |
| Rated Operational Voltage | Auxiliary Circuit 600 V AC/DC |
| Rated Operational Current (I e ) | 16 A |
| Rated Frequency (f) | Main circuit: 50/60 Hz; auxiliary circuit: 50/60 Hz or DC |
| Rated Impulse Withstand Voltage (U imp ) | Auxiliary Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Number of Poles | 3 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Auxiliary Circuit NC 6 A |
| Rated Operational Current AC-15 (I e ) | (120 V) NC 3 A |
| Rated Operational Current DC-13 (I e ) | (125 V) NC 0.55 A |
| Degree of Protection | IP20 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 4 mm² |
| Tightening Torque | Auxiliary Circuit 1 ... 1.2 N·m |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Power Loss | at Rated Operating Conditions per Pole 1.3 ... 2.2 W |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NC:) B600 |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 18-12 AWG |
| Connecting Capacity Auxiliary Circuit UL/CSA | Flexible 1/2x 18-12 AWG |
| Published component type | Thermal overload relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Extended product type | T16-16 |
| Trip class | 10 |
| Auxiliary contacts | 1 normally closed and 1 normally open |
| Main circuit rated operational voltage | 690 V AC |
Les informations du catalogue peuvent comporter des erreurs ou être obsolètes. Les spécifications complètes et les données vérifiées sont disponibles sur demande. Confirmez avec nous la référence et la compatibilité avec votre équipement avant de commander.