Illustration technique — ABB 1SCA022771R7280 — 1SCA022771R7280 — Switch disconnector (low voltage)

Illustration technique. Representative component image; exact configuration and appearance may vary. Images fournies à titre indicatif. L’apparence de la pièce livrée peut varier.

ABB

1SCA022771R7280 — Switch disconnector (low voltage)

Gestion de câbles et transfert d’énergie

Référence de la pièce: 1SCA022771R7280

1SCA022771R7280 — Switch disconnector (low voltage) — ABB reference 1SCA022771R7280. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Vous recherchez ABB 1SCA022771R7280 ? Cette référence de catalogue est classée sous « Gestion de câbles et transfert d’énergie ». Envoyez la référence et les informations sur votre équipement pour vérifier les spécifications et la disponibilité, et obtenir un devis avec livraison incluse.

Disponibilité sur demande

Prix sur devis

Livraison incluseGarantie et serviceObtenir un devis pour cette pièce

Caractéristiques techniques

FabricantABB
Référence de la pièce1SCA022771R7280
CatégorieGestion de câbles et transfert d’énergie
Degree of ProtectionFront IP20
Product Net Width205 mm
Product Net Height150 mm
Product Net Depth / Length160 mm
Product Net Weight4.1 kg
Conventional Free-air Thermal Current (I th )Θ = 40 °C 200 A
Conventional Thermal Current (I the )Fully Enclosed 200 A
Handle ColorBlack
Mounting TypeBase mounting
Number of Poles4P
Operating ModeFront operated
Position of Line TerminalsTop In - Bottom Out, Bottom In - Top Out
Power Lossat Rated Operating Conditions per Pole 4 W
Rated Impulse Withstand Voltage (U imp )12 kV
Rated Insulation Voltage (U i )1000 V
Rated Operational Current AC-21A (I e )(380 ... 415 V) 200 A
Rated Operational Current AC-22A (I e )(380 ... 415 V) 200 A
Rated Operational Current AC-23A (I e )(380 ... 415 V) 200 A
Rated Operational Current AC-31B (I e )(380 ... 415 V) 200 A
Rated Operational Current AC-33B (I e )(380 ... 415 V) 200 A
Rated Operational Power AC-23A (P e )(380 ... 415 V) 110 kW
Rated Operational VoltageMain Circuit 1000 V
Rated Short-time Withstand Current Low Voltage (I cw )for 1 s 8 kiloampere rms
Switches Operating MechanismMechanism at the End of the Switch
Terminal TypeScrew Terminals
Terminal Width20 mm
Tightening Torqueacc. IEC 60947-1 15 ... 22 N·m
Ampere Rating200 A
Published component typeSwitch disconnector (low voltage)
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Les informations du catalogue peuvent comporter des erreurs ou être obsolètes. Les spécifications complètes et les données vérifiées sont disponibles sur demande. Confirmez avec nous la référence et la compatibilité avec votre équipement avant de commander.

Questions sur le produit

Les résultats de recherche pour cette pièce ne sont pas encore disponibles en français. Contactez notre équipe pour obtenir de l’aide.

Obtenir un devis pour cette pièce

Bienvenue chez vous.

Choisissez votre langue et votre destination de livraison. Le prix final et la livraison seront confirmés dans votre devis.