C1042D040Photographie du produit non fournie

Référence de catalogue. Disponibilité, spécifications exactes et fourniture d’origine ou adaptable confirmées dans le devis.

Schneider Electric

C1042D040 — This MicroLogic 2.2 is a 4 poles 4d electronic trip unit used on ComPacT NSX 100/160/250 circuit breakers. This 40A rating electronic trip unit is an optimum choice for all…

Capteurs et automatisation

Référence de la pièce: C1042D040

C1042D040 — This MicroLogic 2.2 is a 4 poles 4d electronic trip unit used on ComPacT NSX 100/160/250 circuit breakers. This 40A rating electronic trip unit is an optimum choice for all… — Schneider Electric reference C1042D040. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Vous recherchez Schneider Electric C1042D040 ? Cette référence de catalogue est classée sous « Capteurs et automatisation ». Envoyez la référence et les informations sur votre équipement pour vérifier les spécifications et la disponibilité, et obtenir un devis avec livraison incluse.

Disponibilité sur demande

Prix sur devis

Livraison incluseGarantie et serviceObtenir un devis pour cette pièce

Caractéristiques techniques

FabricantSchneider Electric
Référence de la pièceC1042D040
CatégorieCapteurs et automatisation
RangeComPacT
Range of productComPacT NSX100...250
Product or component typeTrip unit
Range compatibilityComPacT NSX100 ComPacT NSX160 ComPacT NSX250
Poles description4P
Protected poles description3D + N/2 4D 3D
Trip unit protection functionsLSoI
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Trip unit rating40 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range18...40 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir
Neutral protection settings0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range600 A
Earth-leakage protectionWithout
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Les informations du catalogue peuvent comporter des erreurs ou être obsolètes. Les spécifications complètes et les données vérifiées sont disponibles sur demande. Confirmez avec nous la référence et la compatibilité avec votre équipement avant de commander.

Questions sur le produit

Les résultats de recherche pour cette pièce ne sont pas encore disponibles en français. Contactez notre équipe pour obtenir de l’aide.

Obtenir un devis pour cette pièce

Bienvenue chez vous.

Choisissez votre langue et votre destination de livraison. Le prix final et la livraison seront confirmés dans votre devis.