C1042D100 — This MicroLogic 2.2 is a 4 poles 4d electronic trip unit used on ComPacT NSX 100/160/250 circuit breakers. This 100A rating electronic trip unit is an optimum choice for all…
Capteurs et automatisationRéférence de la pièce: C1042D100
C1042D100 — This MicroLogic 2.2 is a 4 poles 4d electronic trip unit used on ComPacT NSX 100/160/250 circuit breakers. This 100A rating electronic trip unit is an optimum choice for all… — Schneider Electric reference C1042D100. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.
Vous recherchez Schneider Electric C1042D100 ? Cette référence de catalogue est classée sous « Capteurs et automatisation ». Envoyez la référence et les informations sur votre équipement pour vérifier les spécifications et la disponibilité, et obtenir un devis avec livraison incluse.
Disponibilité sur demande
Caractéristiques techniques
| Fabricant | Schneider Electric |
|---|---|
| Référence de la pièce | C1042D100 |
| Catégorie | Capteurs et automatisation |
| Range | ComPacT |
| Range of product | ComPacT NSX100...250 |
| Product or component type | Trip unit |
| Range compatibility | ComPacT NSX100 ComPacT NSX160 ComPacT NSX250 |
| Poles description | 4P |
| Protected poles description | 3D + N/2 4D 3D |
| Trip unit protection functions | LSoI |
| Protection type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
| Trip unit rating | 100 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network frequency | 50/60 Hz |
| Circuit breaker mounting mode | Fixed |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 40...100 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir |
| Neutral protection settings | 0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D) |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 1500 A |
| Earth-leakage protection | Without |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
| Reference status | Published part reference; specification and fitment require confirmation |