LV433892 — This Micrologic 4.2 AL is a 4 poles 4d electronic trip unit used on Compact NSX 250 circuit breakers. This 250A rating electronic trip unit is an optimum choice for all…
Gestion de câbles et transfert d’énergieRéférence de la pièce: LV433892
LV433892 — This Micrologic 4.2 AL is a 4 poles 4d electronic trip unit used on Compact NSX 250 circuit breakers. This 250A rating electronic trip unit is an optimum choice for all… — Schneider Electric reference LV433892. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.
Vous recherchez Schneider Electric LV433892 ? Cette référence de catalogue est classée sous « Gestion de câbles et transfert d’énergie ». Envoyez la référence et les informations sur votre équipement pour vérifier les spécifications et la disponibilité, et obtenir un devis avec livraison incluse.
Disponibilité sur demande
Caractéristiques techniques
| Fabricant | Schneider Electric |
|---|---|
| Référence de la pièce | LV433892 |
| Catégorie | Gestion de câbles et transfert d’énergie |
| Range | ComPact |
| Range of product | ComPact NSX100...250 |
| Product or component type | Trip unit |
| Range compatibility | ComPact NSX250 |
| Number of poles | 4P |
| Protected poles description | 3t 3t + N/2 4t |
| Trip unit protection functions | LSoI |
| Protection type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
| Trip unit rated current | 250 A at 40 °C |
| [Ue] rated operational voltage | 440 V AC 50/60 Hz |
| Network frequency | 50/60 Hz |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 100...250 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| [tsd] Short-time protection delay adjustment range | 0.02 s |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 3000 A |
| Earth-leakage protection | Integrated |
| Earth-leakage protection class | Class A |
| Earth-leakage protection sensitity adjustment type IÎn | Adjustable |
| [IÎn] earth-leakage protection sensitivity adjustment range | 5 A 300 mA 100 mA 500 mA 30 mA 1 A 3 A |
| Earth-leakage protection specific mode | OFF using the IÎn rotary switch |
| Earth-leakage protection time delay adjustement type Ît | Adjustable |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
Les informations du catalogue peuvent comporter des erreurs ou être obsolètes. Les spécifications complètes et les données vérifiées sont disponibles sur demande. Confirmez avec nous la référence et la compatibilité avec votre équipement avant de commander.
Questions sur le produit
Les résultats de recherche pour cette pièce ne sont pas encore disponibles en français. Contactez notre équipe pour obtenir de l’aide.
Obtenir un devis pour cette pièce