Schneider Electric

LV433962 — This Micrologic 4.3 AL is a 4 poles 4d electronic trip unit used on Compact NSX 400/630 circuit breakers. This 400A rating electronic trip unit is an optimum choice for all…

Gestion de câbles et transfert d’énergie

Référence de la pièce: LV433962

LV433962 — This Micrologic 4.3 AL is a 4 poles 4d electronic trip unit used on Compact NSX 400/630 circuit breakers. This 400A rating electronic trip unit is an optimum choice for all… — Schneider Electric reference LV433962. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Vous recherchez Schneider Electric LV433962 ? Cette référence de catalogue est classée sous « Gestion de câbles et transfert d’énergie ». Envoyez la référence et les informations sur votre équipement pour vérifier les spécifications et la disponibilité, et obtenir un devis avec livraison incluse.

Disponibilité sur demande

Prix sur devis

Livraison incluseGarantie et serviceObtenir un devis pour cette pièce

Caractéristiques techniques

FabricantSchneider Electric
Référence de la pièceLV433962
CatégorieGestion de câbles et transfert d’énergie
RangeComPact
Range of productComPact NSX400...630
Product or component typeTrip unit
Range compatibilityComPact NSX400 ComPact NSX630
Number of poles4P
Protected poles description4t 3t 3t + N/2
Trip unit protection functionsLSoI
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Trip unit rated current400 A at 40 °C
[Ue] rated operational voltage440 V AC 50/60 Hz
Network frequency50/60 Hz
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range160...400 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
[tsd] Short-time protection delay adjustment range0.02 s
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range4800 A
Earth-leakage protectionIntegrated
Earth-leakage protection classClass A
Earth-leakage protection sensitity adjustment type IΔnAdjustable
[IΔn] earth-leakage protection sensitivity adjustment range5 A 500 mA 1 A 3 A 10 A 300 mA
Earth-leakage protection specific modeOFF using the IΔn rotary switch
Earth-leakage protection time delay adjustement type ΔtAdjustable
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Les informations du catalogue peuvent comporter des erreurs ou être obsolètes. Les spécifications complètes et les données vérifiées sont disponibles sur demande. Confirmez avec nous la référence et la compatibilité avec votre équipement avant de commander.

Questions sur le produit

Les résultats de recherche pour cette pièce ne sont pas encore disponibles en français. Contactez notre équipe pour obtenir de l’aide.

Obtenir un devis pour cette pièce

Bienvenue chez vous.

Choisissez votre langue et votre destination de livraison. Le prix final et la livraison seront confirmés dans votre devis.