פריט קטלוגי. זמינות, מפרט מדויק ואספקה מקורית או חלופית יאושרו בהצעת המחיר.
C1632D160 — This MicroLogic 2.2 is a 3 poles 3d electronic trip unit used on ComPacT NSX 160/250 circuit breakers. This 160A rating electronic trip unit is an optimum choice for all…
חיישנים ואוטומציהמספר חלק: C1632D160
C1632D160 — This MicroLogic 2.2 is a 3 poles 3d electronic trip unit used on ComPacT NSX 160/250 circuit breakers. This 160A rating electronic trip unit is an optimum choice for all… — Schneider Electric reference C1632D160. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.
מחפשים Schneider Electric C1632D160? פריט קטלוגי זה מופיע בסיווג חיישנים ואוטומציה. שלחו את מספר החלק ופרטי הציוד כדי שנוכל לאמת את המפרט והזמינות ולהכין הצעת מחיר הכוללת משלוח.
זמינות לפי בקשה
מפרט טכני
| יצרן | Schneider Electric |
|---|---|
| מספר חלק | C1632D160 |
| קטגוריה | חיישנים ואוטומציה |
| Range | ComPacT |
| Range of product | ComPacT NSX100...250 |
| Product or component type | Trip unit |
| Range compatibility | ComPacT NSX160 ComPacT NSX250 |
| Poles description | 3P |
| Protected poles description | 3D |
| Trip unit protection functions | LSoI |
| Protection type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
| Trip unit rating | 160 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network frequency | 50/60 Hz |
| Circuit breaker mounting mode | Fixed |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 63...160 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 2400 A |
| Earth-leakage protection | Without |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
המידע בקטלוג עלול להיות לא מדויק או לא מעודכן. מפרט מלא ופרטים מאומתים זמינים לפי בקשה. יש לאשר עמנו את מספר החלק והתאמתו לציוד לפני ההזמנה.
שאלות על המוצר
מידע מחקרי על חלק זה עדיין אינו זמין בעברית. פנו לצוות שלנו לקבלת עזרה.
קבלת הצעת מחיר לחלק זה