Illustrazione tecnica. Representative component image; exact configuration and appearance may vary. Immagini solo di riferimento. L’aspetto del componente fornito può variare.
1SAE232111R0140 — Installation Contactor
contattoreCodice ricambio: 1SAE232111R0140
ABB 1SAE232111R0140 (EN25-40N-01) is a four-pole installation contactor with four normally open main contacts and a 24 V AC/DC control circuit. It is rated 25 A for AC-1 duty and has On, Off and Auto operating positions. The main circuit and load ratings should be checked against the intended application.
Cerchi ABB 1SAE232111R0140? Questa referenza di catalogo è classificata come «contattore». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.
Disponibilità su richiesta
Prezzo su preventivo
Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambioSpecifiche tecniche
| Produttore | ABB |
|---|---|
| Codice ricambio | 1SAE232111R0140 |
| Categoria | Elettricità e controllo |
| Product Net Width | 36 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.25 kg |
| Number of Main Contacts NO | 4 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Rated Operational Voltage | Main circuit: 220 V DC; 400 V AC |
| Rated Frequency (f) | Control circuit: 50, 60 or 400 Hz, or DC; main circuit: 50 or 60 Hz, or DC |
| Rated Operational Current AC-1 (I e ) | (NO) 25 A |
| Rated Operational Current AC-3 (I e ) | 9 A, normally open, at 230 V single-phase or 400 V three-phase |
| Rated Operational Current AC-7a (I e ) | (NO) 25 A |
| Rated Operational Current AC-7b (I e ) | 9 A, normally open, at 230 V single-phase or 400 V three-phase |
| Rated Operational Power AC-1 (P e ) | 5.8 kW at 230 V single-phase; 17.3 kW at 400 V three-phase, normally open |
| Rated Operational Power AC-3 (P e ) | 1.3 kW at 230 V single-phase; 4 kW at 400 V three-phase, normally open |
| Rated Operational Power AC-7a (P e ) | 5.8 kW at 230 V single-phase; 17.3 kW at 400 V three-phase, normally open |
| Rated Operational Power AC-7b (P e ) | 1.3 kW at 230 V single-phase; 4 kW at 400 V three-phase, normally open |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A |
| Rated Insulation Voltage (U i ) | 500 V |
| Rated Impulse Withstand Voltage (U imp ) | 4 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 24 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 2 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Degree of Protection | IP20 |
| Operating Ambient Temperature | -25 to +55 °C |
| Manual operating positions | On, Off, Auto |
| Width in modular spacings | 2 |
Le informazioni del catalogo possono contenere errori o non essere aggiornate. Le specifiche complete e i dati verificati sono disponibili su richiesta. Confermate con noi il codice e la compatibilità con la macchina prima di ordinare.
Domande sul prodotto
Le informazioni ricercate su questo ricambio non sono ancora disponibili in italiano. Contatta il nostro team per assistenza.
Richiedi un preventivo per questo ricambio