Illustrazione tecnica. Representative component image; exact configuration and appearance may vary. Immagini solo di riferimento. L’aspetto del componente fornito può variare.
1SAE232111R0631 — Installation Contactor
contattoreCodice ricambio: 1SAE232111R0631
ABB EN25-31N-06 (1SAE232111R0631) is a four-pole installation contactor with three normally open and one normally closed main contact. Its control circuit is rated at 230–240 V AC/DC, and it offers manual on, off and automatic operation. The 36 mm-wide unit mounts on a DIN rail; verify the load duty and circuit requirements before selection.
Cerchi ABB 1SAE232111R0631? Questa referenza di catalogo è classificata come «contattore». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.
Disponibilità su richiesta
Prezzo su preventivo
Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambioSpecifiche tecniche
| Produttore | ABB |
|---|---|
| Codice ricambio | 1SAE232111R0631 |
| Categoria | Elettricità e controllo |
| Product Net Width | 36 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.24 kg |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Rated Operational Voltage | Main Circuit 220 V DC |
| Rated Frequency (f) | Control Circuit 400 Hz |
| Rated Operational Current AC-1 (I e ) | (NC) 25 A |
| Rated Operational Current AC-3 (I e ) | (230 V) Single Phase, NC 6 A |
| Rated Operational Current AC-7a (I e ) | (NC) 25 A |
| Rated Operational Current AC-7b (I e ) | (230 V) Single Phase, NC 6 A |
| Rated Operational Power AC-1 (P e ) | (230 V) Single Phase, NC 5.8 kW |
| Rated Operational Power AC-3 (P e ) | (230 V) Single Phase, NC 1.3 kW |
| Rated Operational Power AC-7a (P e ) | (230 V) Single Phase, NC 5.8 kW |
| Rated Operational Power AC-7b (P e ) | (230 V) Single Phase, NC 0.9 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A |
| Rated Insulation Voltage (U i ) | 500 V |
| Rated Impulse Withstand Voltage (U imp ) | 4 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 230–240 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 2 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Mounting type | DIN rail |
| Manual operation | On, Off, Auto |
Le informazioni del catalogo possono contenere errori o non essere aggiornate. Le specifiche complete e i dati verificati sono disponibili su richiesta. Confermate con noi il codice e la compatibilità con la macchina prima di ordinare.
Domande sul prodotto
Le informazioni ricercate su questo ricambio non sono ancora disponibili in italiano. Contatta il nostro team per assistenza.
Richiedi un preventivo per questo ricambio