Illustrazione tecnica. Representative component image; exact configuration and appearance may vary. Immagini solo di riferimento. L’aspetto del componente fornito può variare.
1SAE341111R0631 — Installation Contactor
contattoreCodice ricambio: 1SAE341111R0631
ABB 1SAE341111R0631 is an ESB40-31N-06 four-pole installation contactor with three normally open and one normally closed main contacts. It has a rated control voltage of 230 V and a listed AC-1 current of 40 A on the normally open contacts. Check the contact arrangement, load category and circuit ratings before selection.
Cerchi ABB 1SAE341111R0631? Questa referenza di catalogo è classificata come «contattore». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.
Disponibilità su richiesta
Prezzo su preventivo
Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambioSpecifiche tecniche
| Produttore | ABB |
|---|---|
| Codice ricambio | 1SAE341111R0631 |
| Categoria | Elettricità e controllo |
| Product Net Width | 54 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.405 kg |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Rated Operational Voltage | Main circuit: 400 V AC; 220 V DC |
| Rated Frequency (f) | Control circuit: 50 Hz, 60 Hz, 400 Hz and DC; main circuit: 50 Hz, 60 Hz and DC |
| Rated Operational Current AC-1 (I e ) | Normally open: 40 A; normally closed: 30 A |
| Rated Operational Current AC-3 (I e ) | Normally open: 22 A at 230 V single-phase or 400 V three-phase |
| Rated Operational Current AC-7a (I e ) | (NO) 40 A |
| Rated Operational Current AC-7b (I e ) | Normally open: 22 A at 230 V single-phase or 400 V three-phase |
| Rated Operational Power AC-1 (P e ) | (230 V) Single Phase, NC 6.9 kW |
| Rated Operational Power AC-3 (P e ) | (230 V) Single Phase, NO 3.7 kW |
| Rated Operational Power AC-7a (P e ) | (230 V) Single Phase, NC 6.9 kW |
| Rated Operational Power AC-7b (P e ) | (230 V) Single Phase, NO 3.7 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 176 A |
| Rated Insulation Voltage (U i ) | 500 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 230 V |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 3 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Ambient operating temperature | −25 to +55 °C |
| Degree of protection | IP20 |
| Width in modular spacings | 3 |
Le informazioni del catalogo possono contenere errori o non essere aggiornate. Le specifiche complete e i dati verificati sono disponibili su richiesta. Confermate con noi il codice e la compatibilità con la macchina prima di ordinare.
Domande sul prodotto
Le informazioni ricercate su questo ricambio non sono ancora disponibili in italiano. Contatta il nostro team per assistenza.
Richiedi un preventivo per questo ricambio