Illustrazione tecnica. Representative component image; exact configuration and appearance may vary. Immagini solo di riferimento. L’aspetto del componente fornito può variare.
1SAE361111R0620 — Installation Contactors
contattoreCodice ricambio: 1SAE361111R0620
ABB 1SAE361111R0620 is an ESB100-20N-06 two-pole installation contactor with two normally open main contacts and a 230 V AC/DC control coil. Its contacts are rated 100 A for AC-1 and AC-7a use. The DIN-rail mounted device is 54 mm wide and uses screw terminals. Confirm the load, control supply and panel requirements before selection.
Cerchi ABB 1SAE361111R0620? Questa referenza di catalogo è classificata come «contattore». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.
Disponibilità su richiesta
Prezzo su preventivo
Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambioSpecifiche tecniche
| Produttore | ABB |
|---|---|
| Codice ricambio | 1SAE361111R0620 |
| Categoria | Elettricità e controllo |
| Product Net Width | 54 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.405 kg |
| Number of Main Contacts NO | 2 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 2P |
| Rated Operational Voltage | Main circuit: 400 V AC; 220 V DC |
| Rated Frequency (f) | Control circuit: DC, 50, 60 or 400 Hz; main circuit: DC, 50 or 60 Hz |
| Rated Operational Current AC-1 (I e ) | (NO) 100 A |
| Rated Operational Current AC-7a (I e ) | (NO) 100 A |
| Rated Operational Power AC-1 (P e ) | (230 V) Single Phase, NO 23 kW |
| Rated Operational Power AC-7a (P e ) | (230 V) Single Phase, NO 23 kW |
| Rated Insulation Voltage (U i ) | 500 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 150 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 230 V AC/DC |
| Power Loss | at Rated Operating Conditions per Pole 4.2 W |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1x 10 ... 35 mm² |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1x 1 ... 2.5 mm² |
| Wire Stripping Length | Control Circuit 7 mm |
| Degree of Protection | IP20 |
| Tightening Torque | Control Circuit 0.9 N·m |
| Terminal Type | Screw Terminals |
| Published component type | Installation Contactors |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Ambient Air Temperature | Operation: -25 to +55 °C; storage: -40 to +80 °C |
| Width in Number of Modular Spacings | 3 |