Illustrazione tecnica — ABB 1SAM250000R1002 — 1SAM250000R1002 — Motor protection circuit-breaker

Illustrazione tecnica. Representative component image; exact configuration and appearance may vary. Immagini solo di riferimento. L’aspetto del componente fornito può variare.

ABB

1SAM250000R1002 — Motor protection circuit-breaker

Elettricità e controllo

Codice ricambio: 1SAM250000R1002

ABB 1SAM250000R1002 is the MS116-0.25 three-pole manual motor starter, with an adjustable overload setting of 0.16–0.25 A. It provides motor switching and protection against overload, short circuit and phase failure. The device has a rotary handle, trip class 10A and a 50 kA service short-circuit breaking capacity at 400 V AC. It is suitable for single-phase and three-phase applications, subject to correct selection and wiring.

Cerchi ABB 1SAM250000R1002? Questa referenza di catalogo è classificata come «Elettricità e controllo». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.

Disponibilità su richiesta

Prezzo su preventivo

Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambio

Specifiche tecniche

ProduttoreABB
Codice ricambio1SAM250000R1002
CategoriaElettricità e controllo
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter MS116-0.25 valid for production date from week 34/2014
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V -Manual Motor Starter MS116
Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length85.6 mm
Product Net Weight0.225 kg
Rated Service Short-Circuit Breaking Capacity (I cs )50 kA at 400 V AC; 50 kA at 230 V AC
Rated Ultimate Short-Circuit Breaking Capacity (I cu )(230 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (I i )3.1 A
Setting Range0.16–0.25 A
Rated Operational Power AC-3 (P e )0.06 kW at 400 V, three-phase
Rated Operational Power AC-3e (P e )(400 V) Three Phase 0.06 kW
Rated Operational VoltageMain circuit: 690 V AC
Rated Operational Current (I e )0.25 A
Rated Operational Current AC-3 (I e )0.25 A
Rated Operational Current AC-3e (I e )0.25 A
Rated Frequency (f)50/60 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 0.7 ... 1.6 W
Number of Poles3
Conventional Free-air Thermal Current (I th )Main Circuit 0.25 A
Degree of ProtectionHousing IP20; main circuit terminals IP10
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Mounting Position1 ... 6
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Trip Class10A
Mounting35 mm DIN rail, TH35-7.5 or TH35-15

Le informazioni del catalogo possono contenere errori o non essere aggiornate. Le specifiche complete e i dati verificati sono disponibili su richiesta. Confermate con noi il codice e la compatibilità con la macchina prima di ordinare.

Domande sul prodotto