Illustrazione tecnica. Representative component image; exact configuration and appearance may vary. Immagini solo di riferimento. L’aspetto del componente fornito può variare.
1SAM250000R1014 — Motor protection circuit-breaker
Elettricità e controlloCodice ricambio: 1SAM250000R1014
ABB 1SAM250000R1014 is the MS116-25 manual motor starter and motor protection circuit-breaker. It provides manual switching and protection against overload, short circuit and phase failure. The three-pole unit has a 20–25 A adjustable overload range, a 25 A rated operational current and screw terminals. It is intended for single-phase or three-phase motor applications, subject to correct selection and installation.
Cerchi ABB 1SAM250000R1014? Questa referenza di catalogo è classificata come «Elettricità e controllo». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.
Disponibilità su richiesta
Prezzo su preventivo
Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambioSpecifiche tecniche
| Produttore | ABB |
|---|---|
| Codice ricambio | 1SAM250000R1014 |
| Categoria | Elettricità e controllo |
| Time-Current Characteristic Curve | Tripping characteristic - Manual Motor Starter MS116-25 |
| Cut-off Current Characteristic | Cut-off Current Characteristic @ 400V -Manual Motor Starter MS116 |
| Product Net Width | 45 mm |
| Product Net Height | 97.8 mm |
| Product Net Depth / Length | 85.4 mm |
| Product Net Weight | 0.31 kg |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | 10 kA at 230 V AC; 10 kA at 400 V AC |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | (230 V AC) 16 kA |
| Rated Instantaneous Short-Circuit Current Setting (I i ) | 375 A |
| Setting Range | 20–25 A |
| Rated Operational Power AC-3 (P e ) | 11 kW at 400 V, three-phase |
| Rated Operational Power AC-3e (P e ) | (400 V) Three Phase 11 kW |
| Rated Operational Voltage | Main circuit: 690 V AC |
| Rated Operational Current (I e ) | 25 A |
| Rated Operational Current AC-3 (I e ) | 25 A |
| Rated Operational Current AC-3e (I e ) | 25 A |
| Rated Frequency (f) | 50/60 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Main Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 1.8 ... 2.8 W |
| Number of Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 25 A |
| Degree of Protection | Housing IP20; main circuit terminals IP10 |
| Terminal Type | Screw terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm² |
| Tightening Torque | Main Circuit 2 N·m |
| Wire Stripping Length | Main Circuit 10 mm |
| Mounting Position | 1 ... 6 |
| Published component type | Motor protection circuit-breaker |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip Class | 10A |
| Mounting on DIN Rail | TH35-7.5 or TH35-15, 35 mm rail |
Le informazioni del catalogo possono contenere errori o non essere aggiornate. Le specifiche complete e i dati verificati sono disponibili su richiesta. Confermate con noi il codice e la compatibilità con la macchina prima di ordinare.
Domande sul prodotto
Le informazioni ricercate su questo ricambio non sono ancora disponibili in italiano. Contatta il nostro team per assistenza.
Richiedi un preventivo per questo ricambio