Illustrazione tecnica. Representative component image; exact configuration and appearance may vary. Immagini solo di riferimento. L’aspetto del componente fornito può variare.
1SAM350000R1011 — Motor protection circuit-breaker
Elettricità e controlloCodice ricambio: 1SAM350000R1011
ABB 1SAM350000R1011, type MS132-16, is a three-pole manual motor starter and motor protection circuit-breaker with an adjustable 10–16 A overload setting and trip class 10. It provides manual switching and protection against overload, short circuit and phase failure. The device has screw terminals, a lockable rotary handle and a 45 mm wide housing.
Cerchi ABB 1SAM350000R1011? Questa referenza di catalogo è classificata come «Elettricità e controllo». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.
Disponibilità su richiesta
Prezzo su preventivo
Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambioSpecifiche tecniche
| Produttore | ABB |
|---|---|
| Codice ricambio | 1SAM350000R1011 |
| Categoria | Elettricità e controllo |
| Ex Operating Instructions | ATEX - Operating instructions for Manual Motor Starters MS132 for potentially explosive areas |
| Time-Current Characteristic Curve | Tripping characteristic - Manual Motor Starter MS132-16.0 |
| Cut-off Current Characteristic | Cut-off Current Characteristic @ 400V -Manual Motor Starter MS132 |
| Product Net Width | 45 mm |
| Product Net Height | 97.8 mm |
| Product Net Depth / Length | 86.55 mm |
| Product Net Weight | 0.31 kg |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | 100 kA at 230 V AC and 400 V AC; 20 kA at 440 V AC and 500 V AC; 3 kA at 690 V AC; 10 kA at 250 V DC with three poles in series |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | 100 kA at 230 V AC and 400 V AC; 20 kA at 440 V AC and 500 V AC; 3 kA at 690 V AC |
| Rated Instantaneous Short-Circuit Current Setting (I i ) | 240 A |
| Setting Range | 10–16 A |
| Rated Operational Power AC-3 (P e ) | 7.5 kW at 400 V, three-phase |
| Rated Operational Power AC-3e (P e ) | (400 V) Three Phase 7.5 kW |
| Rated Operational Voltage | Main circuit 690 V AC; 250 V DC with three poles in series |
| Rated Operational Current (I e ) | 16 A |
| Rated Operational Current AC-3 (I e ) | 16 A |
| Rated Operational Current AC-3e (I e ) | 16 A |
| Rated Operational Current DC-5 (I e ) | 16 A |
| Rated Frequency (f) | 50/60 Hz |
| Operating Frequency (f sw ) | 0 ... 400 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Main Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 1.1 ... 2.8 W |
| Number of Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 16 A |
| Degree of Protection | Housing IP20; main circuit terminals IP10 |
| Terminal Type | Screw terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm² |
| Published component type | Motor protection circuit-breaker |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Extended product type | MS132-16 |
| Trip class | 10 |
| Rated operational current (Ie) | 16 A |
| Mounting | TH35-7.5 or TH35-15 DIN rail |
| Actuator | Rotary handle with ON/OFF/TRIP indication |
Le informazioni del catalogo possono contenere errori o non essere aggiornate. Le specifiche complete e i dati verificati sono disponibili su richiesta. Confermate con noi il codice e la compatibilità con la macchina prima di ordinare.
Domande sul prodotto
Le informazioni ricercate su questo ricambio non sono ancora disponibili in italiano. Contatta il nostro team per assistenza.
Richiedi un preventivo per questo ricambio