Illustrazione tecnica. Representative component image; exact configuration and appearance may vary. Immagini solo di riferimento. L’aspetto del componente fornito può variare.
1SAM360000R1011 — Motor protection circuit-breaker
relèCodice ricambio: 1SAM360000R1011
ABB 1SAM360000R1011 is the MO132-16 magnetic-only manual motor starter, rated at 16 A. The three-pole device provides manual switching and short-circuit protection and has a lockable rotary handle. A suitable separate thermal or electronic overload relay is required for motor overload protection.
Cerchi ABB 1SAM360000R1011? Questa referenza di catalogo è classificata come «relè». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.
Disponibilità su richiesta
Prezzo su preventivo
Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambioSpecifiche tecniche
| Produttore | ABB |
|---|---|
| Codice ricambio | 1SAM360000R1011 |
| Categoria | Elettricità e controllo |
| Time-Current Characteristic Curve | Tripping characteristic - Manual Motor Starter Magnetic Only MO132-4 ... MO132-32 |
| Cut-off Current Characteristic | Cut-off Current Characteristic @ 400V -Manual Motor Starter MS132 |
| Product Net Width | 45 mm |
| Product Net Height | 97.8 mm |
| Product Net Depth / Length | 86.55 mm |
| Product Net Weight | 0.31 kg |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | (230 V AC) 100 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | (230 V AC) 100 kA |
| Rated Instantaneous Short-Circuit Current Setting (I i ) | 200 A |
| Rated Operational Power AC-3 (P e ) | 7.5 kW at 400 V, three-phase |
| Rated Operational Power AC-3e (P e ) | (400 V) Three Phase 7.5 kW |
| Rated Operational Voltage | Main circuit: 690 V AC |
| Rated Operational Current (I e ) | 16 A |
| Rated Operational Current AC-3 (I e ) | 16 A |
| Rated Operational Current AC-3e (I e ) | 16 A |
| Rated Frequency (f) | Main circuit: 50 / 60 Hz |
| Operating Frequency (f sw ) | 0 ... 400 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Main Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Power Loss | 1.9 W per pole at rated operating conditions |
| Number of Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 16 A |
| Degree of Protection | Housing IP20; main circuit terminals IP10 |
| Terminal Type | Screw terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm² |
| Tightening Torque | Main Circuit 1.5 N·m |
| Wire Stripping Length | Main Circuit 10 mm |
| Mounting Position | 1 ... 6 |
| Published component type | Motor protection circuit-breaker |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Mounting on DIN Rail | TH35-7.5 or TH35-15, 35 mm rail |