Illustrazione tecnica. Representative component image; exact configuration and appearance may vary. Immagini solo di riferimento. L’aspetto del componente fornito può variare.
1SAX111001R1104 — Electronic overload relay
relèCodice ricambio: 1SAX111001R1104
ABB 1SAX111001R1104 is the E16DU-6.3 electronic overload relay for motor overload and phase-failure protection. It is self-supplied, with a 2.0–6.3 A current setting range, selectable 10E, 20E or 30E trip class, and manual or automatic reset. It has one normally closed trip contact and one normally open signal contact.
Cerchi ABB 1SAX111001R1104? Questa referenza di catalogo è classificata come «relè». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.
Disponibilità su richiesta
Prezzo su preventivo
Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambioSpecifiche tecniche
| Produttore | ABB |
|---|---|
| Codice ricambio | 1SAX111001R1104 |
| Categoria | Elettricità e controllo |
| Time-Current Characteristic Curve | Tripping characteristic - Electronic overload relay E16DU, E45DU E80DU, E140DU, E200DU, E320DU, E500DU, E800DU from cold state. Valid for production date from week 49/07 (0497) |
| Product Net Width | 44.4 mm |
| Product Net Height | 74.6 mm |
| Product Net Depth / Length | 57 mm |
| Product Net Weight | 0.15 kg |
| Setting Range | 2.0–6.3 A |
| Rated Operational Voltage | Main circuit: 690 V AC; auxiliary circuit: 600 V AC/DC |
| Rated Operational Current (I e ) | 6.3 A |
| Rated Frequency (f) | Auxiliary Circuit 50 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Auxiliary Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Number of Poles | 3P |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Auxiliary Circuit NC 6 A |
| Rated Operational Current AC-15 (I e ) | (240 V) NC 3 A |
| Rated Operational Current DC-13 (I e ) | (125 V) NC 0.55 A |
| Degree of Protection | IP20 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Tightening Torque | Auxiliary Circuit 0.8 ... 1.2 N·m |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Mounting Position | 1 ... 6 |
| Power Loss | at Rated Operating Conditions per Pole 0.008 ... 0.083 W |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | B600 |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 16-10 AWG |
| Published component type | Electronic overload relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip Class | 10E, 20E or 30E, selectable |
| Reset | Manual or automatic, selectable |
| External Power Supply | Not required; self-supplied |
Le informazioni del catalogo possono contenere errori o non essere aggiornate. Le specifiche complete e i dati verificati sono disponibili su richiesta. Confermate con noi il codice e la compatibilità con la macchina prima di ordinare.
Domande sul prodotto
Le informazioni ricercate su questo ricambio non sono ancora disponibili in italiano. Contatta il nostro team per assistenza.
Richiedi un preventivo per questo ricambio