Riferimento di catalogo. Disponibilità, specifiche esatte e fornitura originale o alternativa sono confermate nel preventivo.
1SAZ211201R2033 — Thermal overload relay
relèCodice ricambio: 1SAZ211201R2033
ABB 1SAZ211201R2033 is a TA25DU-4.0M three-pole thermal overload relay with an adjustable 2.8–4.0 A setting range and trip class 10A. It provides motor overload and phase-failure protection, with temperature compensation, selectable manual or automatic reset, trip indication, STOP and TEST functions, and one normally open and one normally closed auxiliary contact.
Cerchi ABB 1SAZ211201R2033? Questa referenza di catalogo è classificata come «relè». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.
Disponibilità su richiesta
Prezzo su preventivo
Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambioSpecifiche tecniche
| Produttore | ABB |
|---|---|
| Codice ricambio | 1SAZ211201R2033 |
| Categoria | Elettricità e controllo |
| Time-Current Characteristic Curve | Tripping characteristic - Thermal overload relay TA25DU-4.0, TA25DU-4.0 V1000 |
| Product Net Width | 44 mm |
| Product Net Height | 80 mm |
| Product Net Depth / Length | 94 mm |
| Product Net Weight | 0.15 kg |
| Rated Operational Voltage | Main circuit 690 V AC; main circuit 440 V DC |
| Rated Operational Current (I e ) | 4 A |
| Rated Frequency (f) | Auxiliary circuit 50 Hz, 60 Hz and DC; main circuit 50 Hz, 60 Hz and DC |
| Number of Poles | 3P |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Auxiliary Circuit NC 5 A |
| Rated Operational Current AC-15 (I e ) | (120 V) NC 3 A |
| Degree of Protection | Housing IP20; main circuit terminals IP10 |
| Connecting Capacity Auxiliary Circuit | Flexible 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1x 0.75 ... 4 mm² |
| Power Loss | at Rated Operating Conditions per Pole 1.1 ... 2.2 W |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NC:) B600 |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 16-8 AWG |
| Connecting Capacity Auxiliary Circuit UL/CSA | Flexible 1/2x 18-14 AWG |
| Tightening Torque UL/CSA | Auxiliary Circuit 12 in·lb |
| Ambient Air Temperature | Operation −25 to +55 °C; storage −40 to +70 °C |
| Maximum Operating Altitude Permissible | 2000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | 25g 2 shocks 13 ms |
| Published component type | Thermal overload relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Setting Range | 2.8–4.0 A |
| Trip Class | 10A |
| Reset Mode | Selectable manual or automatic |
Le informazioni del catalogo possono contenere errori o non essere aggiornate. Le specifiche complete e i dati verificati sono disponibili su richiesta. Confermate con noi il codice e la compatibilità con la macchina prima di ordinare.
Domande sul prodotto
Le informazioni ricercate su questo ricambio non sono ancora disponibili in italiano. Contatta il nostro team per assistenza.
Richiedi un preventivo per questo ricambio