1SBH137001R1322 — Block Contactor Relay
contattoreCodice ricambio: 1SBH137001R1322
ABB 1SBH137001R1322 (NF22E-13) is a four-pole block contactor relay for switching auxiliary and control circuits. It has two normally open and two normally closed mechanically linked contacts, a 100–250 V AC 50/60 Hz or DC control circuit, built-in surge suppression and screw terminals.
Cerchi ABB 1SBH137001R1322? Questa referenza di catalogo è classificata come «contattore». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.
Disponibilità su richiesta
Prezzo su preventivo
Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambioSpecifiche tecniche
| Produttore | ABB |
|---|---|
| Codice ricambio | 1SBH137001R1322 |
| Categoria | Elettricità e controllo |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 77 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.27 kg |
| Number of Auxiliary Contacts NO | 2 |
| Number of Auxiliary Contacts NC | 2 |
| Number of Poles | 4P |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (I th ) | acc. to IEC 60947-5-1, Θ = 40 °C 16 A |
| Rated Operational Current AC-15 (I e ) | 6 A at 24–127 V; 4 A at 220–240 V; 3 A at 400–440 V; 2 A at 500 V and 690 V |
| Rated Operational Current DC-13 (I e ) | 6 A / 144 W at 24 V; 2.8 A / 134 W at 48 V; 1 A / 72 W at 72 V; 0.55 A / 60 W at 110 V; 0.55 A / 69 W at 125 V; 0.27 A / 60 W at 220 V; 0.27 A / 68 W at 250 V; 0.15 A / 60 W at 400 V; 0.13 A / 65 W at 500 V; 0.1 A / 60 W at 600 V |
| Rated Short-time Withstand Current Low Voltage (I cw ) | for 0.1 s 140 A |
| Rated Insulation Voltage (U i ) | acc. to IEC 60947-5-1 690 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | AC-15: 1200 cycles per hour; DC-13: 900 cycles per hour |
| Maximum Mechanical Switching Frequency | 6000 cycles per hour |
| Rated Control Circuit Voltage (U c ) | 100–250 V AC, 50/60 Hz; 100–250 V DC |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Mounting on DIN Rail | TH35-7.5 and TH35-15, 35 mm rail, IEC 60715 |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Wire Stripping Length | Auxiliary Circuit 10 mm |
| Degree of Protection | IP20 at auxiliary and coil terminals, IEC 60529 |
| Tightening Torque | Auxiliary Circuit 1.2 N·m |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor Relay |
| Published component type | Block Contactor Relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Ambient operating temperature | −40 to +70 °C in free air |
Le informazioni del catalogo possono contenere errori o non essere aggiornate. Le specifiche complete e i dati verificati sono disponibili su richiesta. Confermate con noi il codice e la compatibilità con la macchina prima di ordinare.
Domande sul prodotto
Le informazioni ricercate su questo ricambio non sono ancora disponibili in italiano. Contatta il nostro team per assistenza.
Richiedi un preventivo per questo ricambio