Immagine di riferimento del componente: Published product reference image; series and variants may differ.

Immagine rappresentativa del tipo di componente, non una foto di questo marchio o codice esatto. Confermare le specifiche; il pezzo fornito può avere un aspetto diverso.

Schneider Electric

A9L40301 — This Acti9 iPRD40r surge arrester protects 3P installations. It allows quick replacement of damaged cartridges. This Type 2 device is recommended for high risk level in…

Gestione cavi e trasferimento di energia

Codice ricambio: A9L40301

A9L40301 — This Acti9 iPRD40r surge arrester protects 3P installations. It allows quick replacement of damaged cartridges. This Type 2 device is recommended for high risk level in… — Schneider Electric reference A9L40301. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Cerchi Schneider Electric A9L40301? Questa referenza di catalogo è classificata come «Gestione cavi e trasferimento di energia». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.

Disponibilità su richiesta

Prezzo su preventivo

Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambio

Specifiche tecniche

ProduttoreSchneider Electric
Codice ricambioA9L40301
CategoriaGestione cavi e trasferimento di energia
Range of productIPRD
range of productActi9
product nameActi9 iPRD
Product or component typeSurge arrester with pluggable cartridge
Poles description3P
Remote signallingWith
Signal contacts composition1 SD (1 C/O)
[Ue] rated operational voltage400 V AC (+/- 10 %) at 50/60 Hz
Nominal discharge currentCommon mode: 15 kA (L/PE) Common mode: 15 kA (N/PE)
Maximum discharge currentCommon mode: 40 kA L/PE
[Uc] maximum continuous operating voltageCommon mode: 350 V L/PE
Maximum [Up] voltage protection levelCommon mode <1.6 kV type 2 L/PE
[Ut] temporary overvoltage337 V L/N 5 s withstand 1200 V N/PE 200 ms safe failure mode
Signalling circuit voltage0.25 A/250 V AC 50/60 Hz
Mounting modeClip-on (DIN rail)
Height85 mm
Width54 mm
Depth69 mm
Product weight0.323 kg
[Ipe] Ground residual current0.6 mA 0.003 mA
Connections - terminalsTunnel type terminal (downside) 2.5…35 mm² Tunnel type terminal (upside) 2.5…35 mm²
Tightening torque2.5 N.m
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Le informazioni del catalogo possono contenere errori o non essere aggiornate. Le specifiche complete e i dati verificati sono disponibili su richiesta. Confermate con noi il codice e la compatibilità con la macchina prima di ordinare.

Domande sul prodotto

Le informazioni ricercate su questo ricambio non sono ancora disponibili in italiano. Contatta il nostro team per assistenza.

Richiedi un preventivo per questo ricambio

Sentiti a casa.

Scegli la lingua e la destinazione di consegna. Il prezzo finale e la spedizione saranno confermati nel preventivo.