Immagine di riferimento del componente: Published product/series reference; confirm the exact configuration and supplied appearance.

Immagine rappresentativa del tipo di componente, non una foto di questo marchio o codice esatto. Confermare le specifiche; il pezzo fornito può avere un aspetto diverso.

Schneider Electric

LV429070 — This Micrologic 2.2 is a 3 poles 3d electronic trip unit used on Compact NSX 100/160/250 circuit breakers. This 100A rating electronic trip unit is an optimum choice for all…

Sensori e automazione

Codice ricambio: LV429070

LV429070 — This Micrologic 2.2 is a 3 poles 3d electronic trip unit used on Compact NSX 100/160/250 circuit breakers. This 100A rating electronic trip unit is an optimum choice for all… — Schneider Electric reference LV429070. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Cerchi Schneider Electric LV429070? Questa referenza di catalogo è classificata come «Sensori e automazione». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.

Disponibilità su richiesta

Prezzo su preventivo

Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambio

Specifiche tecniche

ProduttoreSchneider Electric
Codice ricambioLV429070
CategoriaSensori e automazione
RangeComPact
Range of ProductComPact NSX100...250
Product or Component TypeTrip unit
Range CompatibilityComPact NSX100 ComPact NSX160 ComPact NSX250
Number of poles3P
Protected poles description3t
Trip unit protection functionsLSoI
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Trip unit rated current100 A 104 °F (40 °C)
[Ue] rated operational voltage690 V AC 50/60 Hz
Network Frequency50/60 Hz
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range40...100 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range11 s 7.2 x Ir 16 s 6 x Ir 400 s 1.5 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
[tsd] Short-time protection delay adjustment range0.02 s
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range1500 A
Earth-leakage protectionWithout
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Le informazioni del catalogo possono contenere errori o non essere aggiornate. Le specifiche complete e i dati verificati sono disponibili su richiesta. Confermate con noi il codice e la compatibilità con la macchina prima di ordinare.

Domande sul prodotto

Le informazioni ricercate su questo ricambio non sono ancora disponibili in italiano. Contatta il nostro team per assistenza.

Richiedi un preventivo per questo ricambio

Sentiti a casa.

Scegli la lingua e la destinazione di consegna. Il prezzo finale e la spedizione saranno confermati nel preventivo.