Schneider Electric

LV430093 — This TM100G is a 4 poles 4d thermal-magnetic trip unit used on Compact NSX 100/160/250 circuit breakers. This 100A rating thermal-magnetic trip unit is an optimum choice for…

Elettricità e controllo

Codice ricambio: LV430093

LV430093 — This TM100G is a 4 poles 4d thermal-magnetic trip unit used on Compact NSX 100/160/250 circuit breakers. This 100A rating thermal-magnetic trip unit is an optimum choice for… — Schneider Electric reference LV430093. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Cerchi Schneider Electric LV430093? Questa referenza di catalogo è classificata come «Elettricità e controllo». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.

Disponibilità su richiesta

Prezzo su preventivo

Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambio

Specifiche tecniche

ProduttoreSchneider Electric
Codice ricambioLV430093
CategoriaElettricità e controllo
RangeComPact
Range of productComPact NSX100...250 ComPact NSX100...250 DC
Product or component typeTrip unit
Range compatibilityComPact NSX100 ComPact NSX160 ComPact NSX100 DC
Number of poles4P
Protected poles description4t
Trip unit protection functionsLI
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rated current100 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz 750 V DC
Network frequency50/60 Hz
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range120…400 s at 1.5 x In
Short-time protection pick-up adjustment type IsdFixed
[Isd] Short-time protection pick-up adjustment range320 A
Short-time protection delay adjustment type tsdFixed
Earth-leakage protectionWithout
Neutral protection settings1 x Ir (4t)
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Le informazioni del catalogo possono contenere errori o non essere aggiornate. Le specifiche complete e i dati verificati sono disponibili su richiesta. Confermate con noi il codice e la compatibilità con la macchina prima di ordinare.

Domande sul prodotto

Le informazioni ricercate su questo ricambio non sono ancora disponibili in italiano. Contatta il nostro team per assistenza.

Richiedi un preventivo per questo ricambio

Sentiti a casa.

Scegli la lingua e la destinazione di consegna. Il prezzo finale e la spedizione saranno confermati nel preventivo.