LV433803 — This Micrologic 4.2 is a 3 poles 3d electronic trip unit used on Compact NSX 250 circuit breakers. This 250A rating electronic trip unit is an optimum choice for all standard…
Sensori e automazioneCodice ricambio: LV433803
LV433803 — This Micrologic 4.2 is a 3 poles 3d electronic trip unit used on Compact NSX 250 circuit breakers. This 250A rating electronic trip unit is an optimum choice for all standard… — Schneider Electric reference LV433803. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.
Cerchi Schneider Electric LV433803? Questa referenza di catalogo è classificata come «Sensori e automazione». Invia il codice articolo e i dati della macchina per verificare specifiche e disponibilità e ricevere un preventivo con spedizione inclusa.
Disponibilità su richiesta
Prezzo su preventivo
Spedizione inclusaGaranzia e assistenzaRichiedi un preventivo per questo ricambioSpecifiche tecniche
| Produttore | Schneider Electric |
|---|---|
| Codice ricambio | LV433803 |
| Categoria | Sensori e automazione |
| Range | ComPact |
| Range of product | ComPact NSX100...250 |
| Product or component type | Trip unit |
| Range compatibility | ComPact NSX250 |
| Number of poles | 3P |
| Protected poles description | 3t |
| Trip unit protection functions | LSoIR |
| Protection type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection R : for earth-leakage protection |
| Trip unit rated current | 250 A at 40 °C |
| [Ue] rated operational voltage | 440 V AC 50/60 Hz |
| Network frequency | 50/60 Hz |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 100...250 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| [tsd] Short-time protection delay adjustment range | 0.02 s |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 3000 A |
| Earth-leakage protection | Integrated |
| Earth-leakage protection class | Class A |
| Earth-leakage protection sensitity adjustment type IÎn | Adjustable |
| [IÎn] earth-leakage protection sensitivity adjustment range | 300 mA 30 mA 1 A 100 mA 3 A 500 mA 5 A |
| Earth-leakage protection specific mode | OFF using the IÎn rotary switch |
| Earth-leakage protection time delay adjustement type Ît | Adjustable |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |