技術図 — ABB 1SAM360000R1010 — 1SAM360000R1010 — Motor protection circuit-breaker

技術図. Representative component image; exact configuration and appearance may vary. 画像は参考用です。納入される部品の外観は異なる場合があります。

ABB

1SAM360000R1010 — Motor protection circuit-breaker

リレー

部品番号: 1SAM360000R1010

ABB MO132-10 (1SAM360000R1010) is a three-pole, magnetic-only manual motor starter rated at 10 A. It provides manual switching and short-circuit protection with a disconnect function. An appropriate separate thermal or electronic overload relay is required for motor overload protection.

ABB 1SAM360000R1010をお探しですか。このカタログ参照品は「リレー」に分類されています。部品番号と機械の情報をお送りください。仕様と供給状況を確認し、送料込みのお見積もりをご案内します。

在庫状況はお問い合わせください

価格はお見積もりにて

送料込み保証・サービスこの部品の見積もりを依頼

技術仕様

メーカーABB
部品番号1SAM360000R1010
カテゴリー電装・制御部品
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter Magnetic Only MO132-4 ... MO132-32
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V -Manual Motor Starter MS132
Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length86.75 mm
Product Net Weight0.265 kg
Rated Service Short-Circuit Breaking Capacity (I cs )(230 V AC) 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (I cu )(230 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (I i )125 A
Rated Operational Power AC-3 (P e )4 kW at 400 V, three-phase
Rated Operational Power AC-3e (P e )(400 V) Three Phase 4 kW
Rated Operational VoltageMain circuit: 690 V AC
Rated Operational Current (I e )10 A
Rated Operational Current AC-3 (I e )10 A
Rated Operational Current AC-3e (I e )10 A
Rated Frequency (f)Main circuit: 50/60 Hz
Operating Frequency (f sw )0 ... 400 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 2.2 W
Number of Poles3P
Conventional Free-air Thermal Current (I th )Main Circuit 10 A
Degree of ProtectionHousing IP20; main circuit terminals IP10
Terminal TypeScrew terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Mounting Position1 ... 6
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Mounting on DIN RailTH35-7.5 or TH35-15, 35 mm rail
Overload protectionSeparate appropriate thermal or electronic overload relay required for motor overload protection
Protection typeMagnetic short-circuit protection

カタログ情報には誤りや古い情報が含まれる場合があります。完全な仕様と確認済みの詳細情報はお問い合わせください。ご注文前に部品番号とお使いの機械への適合を当社にご確認ください。

製品に関するご質問

この部品に関する調査情報は、まだ日本語ではご用意できていません。担当チームにお問い合わせください。

この部品の見積もりを依頼

ご利用環境に合わせて設定。