1SAZ411201R2001製品写真は提供されていません
カタログ参照品です。在庫状況、正確な仕様、純正品または代替品の供給は見積書で確認します。
ABB
1SAZ411201R2001 — Thermal overload relay
リレー部品番号: 1SAZ411201R2001
ABB 1SAZ411201R2001 is the TA110DU-90M three-pole thermal overload relay for motor protection. It has trip class 10A, three protected poles and one normally open plus one normally closed auxiliary contact. Confirm the current setting range and compatibility with the existing contactor and motor before ordering.
ABB 1SAZ411201R2001をお探しですか。このカタログ参照品は「リレー」に分類されています。部品番号と機械の情報をお送りください。仕様と供給状況を確認し、送料込みのお見積もりをご案内します。
在庫状況はお問い合わせください
技術仕様
| メーカー | ABB |
|---|---|
| 部品番号 | 1SAZ411201R2001 |
| カテゴリー | 電装・制御部品 |
| Product Net Width | 80 mm |
| Product Net Height | 120 mm |
| Product Net Depth / Length | 120 mm |
| Product Net Weight | 0.75 kg |
| Setting Range | 65 ... 90 A |
| Rated Operational Voltage | Main circuit: 690 V AC or 440 V DC; auxiliary circuit: 500 V AC or 440 V DC |
| Rated Operational Current (I e ) | 90 A |
| Rated Frequency (f) | Auxiliary Circuit 50 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Auxiliary Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Number of Poles | 3P |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Auxiliary Circuit NC 5 A |
| Rated Operational Current AC-15 (I e ) | (120 V) NC 3 A |
| Rated Operational Current DC-13 (I e ) | (125 V) NC 0.25 A |
| Degree of Protection | Housing: IP20; main circuit terminals: IP10 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Flexible 1x 16 ... 35 mm² |
| Tightening Torque | Auxiliary Circuit 1 ... 1.3 N·m |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Power Loss | at Rated Operating Conditions per Pole 2.4 ... 4.5 W |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 6-2/0 AWG |
| Connecting Capacity Auxiliary Circuit UL/CSA | Flexible 1/2x 18-14 AWG |
| Tightening Torque UL/CSA | Auxiliary Circuit 12 in·lb |
| Ambient Air Temperature | Operation: -25 to +55 °C; storage: -40 to +70 °C |
| Published component type | Thermal overload relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip class | 10A |
| Ambient Air Temperature Compensation | Yes |
カタログ情報には誤りや古い情報が含まれる場合があります。完全な仕様と確認済みの詳細情報はお問い合わせください。ご注文前に部品番号とお使いの機械への適合を当社にご確認ください。
製品に関するご質問
この部品に関する調査情報は、まだ日本語ではご用意できていません。担当チームにお問い合わせください。
この部品の見積もりを依頼