ABB
1SAZ421301R1002 — Thermal overload relay
リレー部品番号: 1SAZ421301R1002
ABB 1SAZ421301R1002 is a TA200DU-110-V1000 three-pole thermal overload relay with an adjustable 80–110 A current range and class 10A tripping. It provides motor overload and phase-loss protection and features selectable manual or automatic reset, a normally closed trip contact and a normally open signal contact.
ABB 1SAZ421301R1002をお探しですか。このカタログ参照品は「リレー」に分類されています。部品番号と機械の情報をお送りください。仕様と供給状況を確認し、送料込みのお見積もりをご案内します。
在庫状況はお問い合わせください
技術仕様
| メーカー | ABB |
|---|---|
| 部品番号 | 1SAZ421301R1002 |
| カテゴリー | 電装・制御部品 |
| Ex Operating Instructions | Operating instructions - Thermal overload relay TA200DU V1000 |
| Time-Current Characteristic Curve | Tripping characteristic - Thermal overload relay TA200DU-110, TA200DU-110 V1000 |
| Product Net Width | 104 mm |
| Product Net Height | 151 mm |
| Product Net Depth / Length | 126 mm |
| Product Net Weight | 0.76 kg |
| Setting Range | 80–110 A |
| Rated Operational Voltage | Main circuit: 690 V AC / 440 V DC; auxiliary circuit: 500 V AC / 440 V DC |
| Rated Operational Current (I e ) | 110 A |
| Rated Frequency (f) | Auxiliary Circuit 50 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Auxiliary Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Number of Poles | 3 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Auxiliary Circuit NC 10 A |
| Rated Operational Current AC-15 (I e ) | (120 V) NC 3 A |
| Rated Operational Current DC-13 (I e ) | (125 V) NC 0.25 A |
| Degree of Protection | Housing: IP20; main-circuit terminals: IP00 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Hole Diameter > 10 mm² |
| Tightening Torque | Auxiliary Circuit 1 ... 1.3 N·m |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Mounting Position | 1 ... 6 |
| Power Loss | at Rated Operating Conditions per Pole 2.5 ... 4.7 W |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NO:) B600 |
| Published component type | Thermal overload relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip class | 10A |
| Reset method | Selectable manual or automatic |