技術図. Representative component image; exact configuration and appearance may vary. 画像は参考用です。納入される部品の外観は異なる場合があります。
ABB
1SAZ421301R1005 — Thermal overload relay
リレー部品番号: 1SAZ421301R1005
ABB 1SAZ421301R1005, type TA200DU-175-V1000, is a three-pole thermal overload relay for motor overload and phase-loss protection. It has a 130–175 A adjustable current range, class 10A trip characteristic, one normally closed and one normally open auxiliary contact, and selectable manual or automatic reset.
ABB 1SAZ421301R1005をお探しですか。このカタログ参照品は「リレー」に分類されています。部品番号と機械の情報をお送りください。仕様と供給状況を確認し、送料込みのお見積もりをご案内します。
在庫状況はお問い合わせください
技術仕様
| メーカー | ABB |
|---|---|
| 部品番号 | 1SAZ421301R1005 |
| カテゴリー | 電装・制御部品 |
| Ex Operating Instructions | Operating instructions - Thermal overload relay TA200DU V1000 |
| Time-Current Characteristic Curve | Tripping characteristic - Thermal overload relay TA200DU-175, TA200DU-175 V1000 |
| Product Net Width | 104 mm |
| Product Net Height | 151 mm |
| Product Net Depth / Length | 126 mm |
| Product Net Weight | 0.77 kg |
| Setting Range | 130–175 A |
| Rated Operational Voltage | Auxiliary Circuit 440 V DC |
| Rated Operational Current (I e ) | 175 A |
| Rated Frequency (f) | Auxiliary Circuit 50 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Auxiliary Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Number of Poles | 3 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Auxiliary Circuit NC 10 A |
| Rated Operational Current AC-15 (I e ) | (120 V) NC 3 A |
| Rated Operational Current DC-13 (I e ) | (125 V) NC 0.25 A |
| Degree of Protection | Housing IP20; main circuit terminals IP00 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Hole Diameter > 10 mm² |
| Tightening Torque | Auxiliary Circuit 1 ... 1.3 N·m |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Mounting Position | 1 ... 6 |
| Power Loss | at Rated Operating Conditions per Pole 3.8 ... 6.9 W |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NO:) B600 |
| Published component type | Thermal overload relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip Class | 10A |
| Auxiliary Contacts | 1 normally open and 1 normally closed |
| Reset Method | Selectable manual or automatic |
カタログ情報には誤りや古い情報が含まれる場合があります。完全な仕様と確認済みの詳細情報はお問い合わせください。ご注文前に部品番号とお使いの機械への適合を当社にご確認ください。
製品に関するご質問
この部品に関する調査情報は、まだ日本語ではご用意できていません。担当チームにお問い合わせください。
この部品の見積もりを依頼