1SBE111111R1411 — Installation Contactor
電磁接触器部品番号: 1SBE111111R1411
ABB 1SBE111111R1411 (ESB16-11N-14) is a two-pole installation contactor with one normally open and one normally closed main contact and a 12 V AC/DC control coil. It is rated 16 A for AC-1 and AC-7a loads. The 18 mm-wide unit mounts on a 35 mm DIN rail; select it according to the load category and circuit conditions.
ABB 1SBE111111R1411をお探しですか。このカタログ参照品は「電磁接触器」に分類されています。部品番号と機械の情報をお送りください。仕様と供給状況を確認し、送料込みのお見積もりをご案内します。
在庫状況はお問い合わせください
技術仕様
| メーカー | ABB |
|---|---|
| 部品番号 | 1SBE111111R1411 |
| カテゴリー | 電装・制御部品 |
| Product Net Width | 18 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.14 kg |
| Number of Main Contacts NO | 1 |
| Number of Main Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 2P |
| Rated Operational Voltage | Main circuit: 250 V AC; 220 V DC |
| Rated Frequency (f) | Control circuit: DC, 50 Hz, 60 Hz or 400 Hz; main circuit: DC, 50 Hz or 60 Hz |
| Rated Operational Current AC-1 (I e ) | 16 A, NO and NC |
| Rated Operational Current AC-3 (I e ) | 6 A, 230 V single phase, NO and NC |
| Rated Operational Current AC-7a (I e ) | 16 A, NO and NC |
| Rated Operational Current AC-7b (I e ) | 6 A, 230 V single phase, NO and NC |
| Rated Operational Power AC-1 (P e ) | 3.7 kW, 230 V single phase, NO and NC |
| Rated Operational Power AC-3 (P e ) | 0.9 kW, 230 V single phase, NO and NC |
| Rated Operational Power AC-7a (P e ) | 3.7 kW, 230 V single phase, NO and NC |
| Rated Operational Power AC-7b (P e ) | 0.9 kW, 230 V single phase, NO and NC |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A |
| Rated Insulation Voltage (U i ) | 400 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 12 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 0.9 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Mounting | 35 mm DIN rail, TH35-7.5 or TH35-15 |
| Degree of Protection | IP20 |
| Terminal Type | Screw terminals |
| Width in Number of Modular Spacings | 1 |