技術図. Published product/series reference; confirm the exact configuration and supplied appearance. 画像は参考用です。納入される部品の外観は異なる場合があります。
ABB
1SBE122111R0120 — Installation Contactor
電磁接触器部品番号: 1SBE122111R0120
ABB 1SBE122111R0120 is an EN20-20N-01 two-pole installation contactor with two normally open main contacts and a 24 V AC/DC control coil. It has a manual/automatic toggle and integrated overvoltage protection. The AC-1 rating is 20 A; ratings vary with the load and utilization category.
ABB 1SBE122111R0120をお探しですか。このカタログ参照品は「電磁接触器」に分類されています。部品番号と機械の情報をお送りください。仕様と供給状況を確認し、送料込みのお見積もりをご案内します。
在庫状況はお問い合わせください
技術仕様
| メーカー | ABB |
|---|---|
| 部品番号 | 1SBE122111R0120 |
| カテゴリー | 電装・制御部品 |
| Product Net Width | 18 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.14 kg |
| Number of Main Contacts NO | 2 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 2P |
| Rated Operational Voltage | Main circuit: 250 V AC; 220 V DC |
| Rated Frequency (f) | Control circuit: 50 Hz, 60 Hz, 400 Hz or DC; main circuit: 50 Hz, 60 Hz or DC |
| Rated Operational Current AC-1 (I e ) | 20 A, normally open |
| Rated Operational Current AC-3 (I e ) | 9 A at 230 V, single-phase, normally open |
| Rated Operational Current AC-7a (I e ) | (NO) 20 A |
| Rated Operational Current AC-7b (I e ) | (230 V) Single Phase, NO 9 A |
| Rated Operational Power AC-1 (P e ) | (230 V) Single Phase 4.6 kW |
| Rated Operational Power AC-3 (P e ) | (230 V) Single Phase 1.3 kW |
| Rated Operational Power AC-7a (P e ) | (230 V) Single Phase 4.6 kW |
| Rated Operational Power AC-7b (P e ) | (230 V) Single Phase 1.3 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A |
| Rated Insulation Voltage (U i ) | 400 V |
| Rated Impulse Withstand Voltage (U imp ) | 4 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 24 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 1.4 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Mounting on DIN Rail | TH35-7.5 or TH35-15 |
| Terminal Type | Screw terminals |
| Degree of Protection | IP20 |
カタログ情報には誤りや古い情報が含まれる場合があります。完全な仕様と確認済みの詳細情報はお問い合わせください。ご注文前に部品番号とお使いの機械への適合を当社にご確認ください。