技術図. Representative component image; exact configuration and appearance may vary. 画像は参考用です。納入される部品の外観は異なる場合があります。
ABB
1SFL607102R1111 — Block Contactor
電磁接触器部品番号: 1SFL607102R1111
1SFL607102R1111 — Block Contactor — ABB reference 1SFL607102R1111. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.
ABB 1SFL607102R1111をお探しですか。このカタログ参照品は「電磁接触器」に分類されています。部品番号と機械の情報をお送りください。仕様と供給状況を確認し、送料込みのお見積もりをご案内します。
在庫状況はお問い合わせください
技術仕様
| メーカー | ABB |
|---|---|
| 部品番号 | 1SFL607102R1111 |
| カテゴリー | 電装・制御部品 |
| Product Net Width | 184 mm |
| Product Net Depth / Length | 180 mm |
| Product Net Height | 225 mm |
| Product Net Weight | 5.7 kg |
| Number of Main Contacts NO | 4 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 4P |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Frequency (f) | Main Circuit 50 Hz |
| Conventional Free-air Thermal Current (I th ) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 525 A |
| Rated Operational Current AC-1 (I e ) | (1000 V) 40 °C 400 A |
| Rated Operational Current AC-3 (I e ) | (415 V) 55 °C 370 A |
| Rated Operational Power AC-3 (P e ) | (415 V) 200 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2960 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 5000 A |
| Rated Insulation Voltage (U i ) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V |
| Rated Impulse Withstand Voltage (U imp ) | Main Circuit 8 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Maximum Mechanical Switching Frequency | 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
| Rated Control Circuit Voltage (U c ) | 50 Hz 24 ... 60 V |
| Power Loss | at Rated Operating Conditions per Pole 72 W |
| Operate Time | Between Coil De-energization and NO Contact Opening 45 ... 80 ms |
| Connecting Capacity Main Circuit | Flexible 1 x 16 ... 240 mm² |
| Published component type | Block Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
カタログ情報には誤りや古い情報が含まれる場合があります。完全な仕様と確認済みの詳細情報はお問い合わせください。ご注文前に部品番号とお使いの機械への適合を当社にご確認ください。
製品に関するご質問
この部品に関する調査情報は、まだ日本語ではご用意できていません。担当チームにお問い合わせください。
この部品の見積もりを依頼