部品タイプを示す参考画像であり、このブランドや部品番号そのものの写真ではありません。仕様をご確認ください。納入品の外観は異なる場合があります。
Schneider Electric
NJGF36250U31XTW — Circuit breaker
電装・制御部品部品番号: NJGF36250U31XTW
NJGF36250U31XTW — Circuit breaker — Schneider Electric reference NJGF36250U31XTW. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.
Schneider Electric NJGF36250U31XTWをお探しですか。このカタログ参照品は「電装・制御部品」に分類されています。部品番号と機械の情報をお送りください。仕様と供給状況を確認し、送料込みのお見積もりをご案内します。
在庫状況はお問い合わせください
技術仕様
| メーカー | Schneider Electric |
|---|---|
| 部品番号 | NJGF36250U31XTW |
| カテゴリー | 電装・制御部品 |
| Range of product | PowerPact multistandard |
| Range | PowerPact |
| product name | J-Frame |
| Product or component type | Circuit breaker |
| Poles description | 3P |
| Mounting mode | Unit mount |
| Mounting support | DIN rail Flush Backplate |
| Electrical connection | Terminal nut, line side Terminal nut, load side |
| [In] rated current | 250 A at 40 °C |
| [Ui] rated insulation voltage | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 525 V AC 50/60 Hz conforming to IEC 60947-2 690 V AC 50/60 Hz conforming to IEC 947-2 600 V AC 50/60 Hz conforming to UL 489 |
| Breaking capacity code | JG |
| Connection pitch | 45 mm |
| Local signalling | ON/OFF indication |
| Trip unit protection functions | LI |
| Trip unit rating | 250 A |
| Thermal memory | 20 mn |
| Display type | 3 LEDs |
| Breaking capacity | Icu: 65 kA at 220/240 V - AC conforming to IEC 947-2 Icu: 35 kA at 380/415 V - AC conforming to IEC 947-2 Icu: 35 kA at 440/480 V - AC conforming to IEC 947-2 Icu: 18 kA at 500/525 V - AC conforming to IEC 947-2 65 kA at 240 V - AC conforming to UL 489 35 kA at 480 V - AC conforming to UL 489 18 kA at 600 V - AC conforming to UL 489 |
| [Ics] rated service breaking capacity | Ics: 65 kA at 220/240 V - AC conforming to IEC 947-2 Ics: 35 kA at 380/415 V - AC conforming to IEC 947-2 Ics: 35 kA at 440/480 V - AC conforming to IEC 947-2 Ics: 18 kA at 500/525 V - AC conforming to IEC 947-2 |
| Long time pick-up adjustment range | 0.28...1 x In |
| [tr] long-time delay adjustment range | 16 s 4 s 0.5 s 2 s 1 s 8 s |
| Instantaneous pick-up adjustment range | 1.5...15 x In |
| Overvoltage category | II |
| Height | 191 mm |
| Width | 104 mm |
| Depth | 86 mm |
| Published component type | Circuit breaker |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
カタログ情報には誤りや古い情報が含まれる場合があります。完全な仕様と確認済みの詳細情報はお問い合わせください。ご注文前に部品番号とお使いの機械への適合を当社にご確認ください。